Using the DNP 3.00 Protocol
ION 7500 / ION 7600 User’s Guide
Page 84
Chapter 3 - Default Meter Functionality
DNP Options Module Settings
The DNP Options module provides global settings that affect all DNP Slave Export
and DNP Slave Import modules. The default settings in this module are shown in
the following table.
Importing Data using DNP 3.00
Data can be imported into the meter from a DNP control relay or analog output
device. DNP Slave Import modules are used to take a DNP Analog output or
Binary output object and map them into ION registers. Refer to the DNP Slave
Import module description in the online ION Programmer’s Reference for details.
Setup Register
Setting
Function
BinInStatic
Single-bit Binary Input
variant for Binary Input Static objects
BinInEvents
Binary Input Change w/o time
variant for Binary Input Event objects
BinInEvDepth
100
maximum number of Binary Input Events that can be stored
BinCntStatic
16-bit Binary Counter w/o flag
variant for Binary Counter Static objects
FrzCntStatic
16-bit Frozen Counter w/o flag
variant for Frozen Counter Static objects
FrzCntEvents
16-bit Frozen Counter Event w/o time
variant for Frozen Counter Event objects
FrzCntEvDepth
100
maximum number of Frozen Counter Events that can be stored
CntChangeEvents
16-bit Counter Change Event w/o time
variant for Counter Change Event objects
CntChangeEvDepth
100
maximum number of Counter Change Events that can be stored
AIStatic
16-bit Analog Input w/o flag
variant for Analog Input Static objects
FrzAIStatic
16-bit Frozen Analog Input w/o flag
variant returned from Class 0 poll for Frozen Analog Input Static
objects
FrzAIEvents
16-bit Frozen Analog Event w/o time
variant for Frozen Analog Input Event objects
FrzAIEvDepth
100
maximum number of Frozen Analog Input Events that can be stored
AIChangeEvents
16-bit Analog Input Change Event w/o time
variant for Analog Input Change Event objects
AIChangeEvDepth
200
maximum number of Analog Input Change Events that can be stored
AOStatic
16-bit Analog Output Status
variant for Analog Output Block objects
SelectTimeout
10
Select Before Operate timeout period (in seconds)
TimeSynchPeriod
86400
time (in seconds) between IED requests for time syncs
ALFragSize
2048
maximum application layer message size (in octets) that IED can send
DLAck
Never
when device will request data link layer acknowledgements
DLTimeout
2
how long data link layer waits for acknowledgement from Master
DLNumRetries
0
how many times a data link layer packet is re-sent after failing