DNP Slave Export Module Settings
The factory-configured DNP Slave Export modules are configured as shown in the
following table.
As the table indicates, some of the setup register settings vary for different
modules. Specifically, BasePoint differs for each module within a group (Analog
Input and Binary Counter are groups), and StaticObj is set to Analog Input for the
11 analog input points and Binary Counter for the three binary counter points.
(StaticObj defines the type of DNP object the module provides when the Master
polls it.)
In addition, Scaling is
OFF
for all but two modules. The only modules that apply
scaling are the Analog Input points that provide Voltage and Current Unbalance
data (labeled Unbalx10) and Frequency data (Labeled Freqx10). These modules
apply x10 scaling.
Setup Register
Setting
BasePoint
Varies – each analog input or binary counter has a different BasePoint
StaticObj
11 modules are
Analog Input
; three are
Binary Counter
EventObj
Disable Event Objects
Deadband
0
FrozStaObj
Disable Frozen Static Objects
FrozEvtObj
Disable Frozen Event Objects
EventClass
Class 1
Scaling
OFF (excluding
Unbalx10
and
Freqx10
which are ON)
IONZero
0
IONFull
0 (1000 for
Unbalx10
and 100 for
Freqx10
)
DNPZero
0
DNPFull
0 (10000 for
Unbalx10
and 1000 for
Freqx10
)