Cpc072, Roduct, Pecifications – Goodman Mfg SS-CPC36-72 User Manual
Page 7

6
www.goodmanmfg.com
SS-CPC36-72
SS-CPC36-72
www.goodmanmfg.com
7
P
roduct
S
PecificationS
P
roduct
S
PecificationS
p
rodUCt
s
peCifiCations
— CpC072
CPC072
***3B***B*
CPC072
***3B***C*
CPC072
***4B***B*
CPC072
***4B***C*
CPC072
***7B***B*
CPC072
***7B***C*
Cooling Capacity
Total BTU/h
71,000
71,000
71,000
71,000
71,000
71,000
Sensible BTU/h
48,280
49,800
48,280
49,800
48,280
49,800
EER / IEER
11.2 / 11.4
11.2 / 11.4
11.2 / 11.4
11.2 / 11.4
11.2 / 11.4
11.2 / 11.4
Decibels
78.0
78.0
78.0
78.0
78.0
78.0
AHRI Number
3397631
5582881
3397631
5582881
3397631
5582881
Evaporator Motor / Coil
Motor Type
Belt Drive
Belt Drive
Belt Drive
Belt Drive
Belt Drive
Belt Drive
Wheel (D x W)
1 (11" x 10")
1 (11" x 10")
1 (11" x 10")
1 (11" x 10")
1 (11" x 10")
1 (11" x 10")
Indoor Nominal CFM
2,350
2,350
2,350
2,350
2,350
2,350
Indoor Motor FLA (Cooling)
5.0
5.0
2.5
2.5
2.3
2.3
Horsepower - RPM
1.5-1,725
1.5-1,725
1.5-1,725
1.5-1,725
1.5-1,725
1.5-1,725
Piston Size (Cooling)
0.094
0.094
0.094
0.094
0.094
0.094
Filter Size
(4) 16" x 20" x 2" (4) 16" x 20" x 2" (4) 16" x 20" x 2" (4) 16" x 20" x 2" (4) 16" x 20" x 2" (4) 16" x 20" x 2"
Drain Size (NPT)
¾"
¾"
¾"
¾"
¾"
¾"
R-410A Refrigerant Charge Cir #1(oz.)
213.0
146.0
213.0
146.0
213.0
146.0
Evaporator Coil Face Area (ft²)
8.9
8.9
8.9
8.9
8.9
8.9
Rows Deep/ Fins per Inch
4/ 16
4/ 16
4/ 16
4/ 16
4/ 16
4/ 16
Motor Sheave
VL44 X 7/8
VL44 X 7/8
VL44 X 7/8
VL44 X 7/8
VL44 X 7/8
VL44 X 7/8
Blower Sheave
AK59 X 1
AK59 X 1
AK59 X 1
AK59 X 1
AK59 X 1
AK59 X 1
Belt
AX53
AX53
AX53
AX53
AX53
AX53
Condenser Fan / Coil
Quantity of condenser Fan Motors
1
1
1
1
1
1
Horsepower - RPM
⅓ - 1,075
⅓ - 1,075
⅓ - 1,075
⅓ - 1,075
⅓ - 1,075
⅓ - 1,075
Fan Diameter/ # Fan Blades
22/ 4
22/ 4
22/ 4
22/ 4
22/ 4
22/ 4
Outdoor Nominal CFM
4,200
4,200
4,200
4,200
4,200
4,200
Face Area (ft²)
18.7
19
18.7
19
18.7
19
Rows Deep/ Fins per Inch
2/ 20
2 /27
2/ 20
2 /27
2/ 20
2 /27
Compressor
Quantity / Type
1 / Scroll
1 / Scroll
1 / Scroll
1 / Scroll
1 / Scroll
1 / Scroll
Stage
Single
Single
Single
Single
Single
Single
Compressor RLA / LRA
19/123.0
19/123.0
9.7/62.0
9.7/62.0
7.4/50.0
7.4/50.0
Electrical Data
Voltage/Phase/ Frequency
208-230/3/60
208-230/3/60
460/3/60
460/3/60
575/3/60
575/3/60
Quantity of Compressors
1
1
1
1
1
1
Belt-Driven Standard Max Static
1.0
1.0
1.0
1.0
1.0
1.0
Outdoor Fan FLA
1.90
1.90
1.20
1.20
0.90
0.90
Total Unit Amps
25.9
25.9
13.4
13.4
10.6
10.6
Min. Circuit Ampacity¹
31
31
16
16
12
12
Max. Overcurrent Protection (amps)²
45
45
25
25
15
15
Entrance Power Supply
1.125"
1.125"
1.125"
1.125"
1.125"
1.125"
Entrance Control Voltage
½"
½"
½"
½"
½"
½"
Operating Weight (lbs)
640
625
640
625
640
625
Ship Weight (lbs)
665
650
665
650
665
650
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Notes
• Always check the S&R plate for electrical data on the unit being installed.
• When a factory-installed powered convenience outlet is installed in the equipment, the unit MCA (Min. Circuit Ampacity) will increase by 7.5A for
208/230V units, increase by 3.75A for 460V units, and by 3A for 575V units. The MOP (Max. Overcurrent Protection) device must be sized accordingly.