Installation instructions, Commissioning – Stovax 8455 User Manual
Page 18
18
1. COMMISSIONING
1.1 Close all windows and doors to the room, check all controls,
and allow fire to burn on maximum for 5 minutes. Test for
spillage of flue products using a smoke match. For standard
VFC fires, pass the lighted smoke match along the top front
edge just inside the opening or canopy. For the RD VFC only,
hold the lighted smoke match centrally inside the flue
opening. See Diagram 1 for Radiant fires and 2 for Convector
fires.
1
AR0187
2
AR0179
1.2 If the fire spills, run for a further 10 minutes and re-check. If
there is still spillage, disconnect the fire and seek expert
advice.
1.3 If there are extractor fans in the room or adjacent rooms, the
spillage test must be repeated with the extractors running on
maximum.
1.4 For RD VFC: If spillage is detected and no air vent is fitted in
the room, re-check for spillage with a window slightly open. If
this cures the spillage, it will be necessary to fit a vent.
IF SPILLAGE PERSISTS, DISCONNECT THE APPLIANCE AND
SEEK EXPERT ADVICE.
For future reference record the installation details on the
commissioning sheet on page 3 of these Instructions.