SECTION 3.2

OPERATIONAL ANALYSIS

PART 3

Page 3.2-7

V-TYPE PREPACKAGED

TRANSFER SWITCHES

UTILITY RESTORED, TRANSFER SWITCH DE-E

ENERGIZED

After the preset time interval expires the circuit board will open the Wire 23 circuit to ground. The transfer relay
de-energizes, it’s normally closed contacts close, and utility source voltage is delivered to the utility closing coil
(C1), via Wires N1A and N2A, closed Transfer Relay Contacts 1 and 7, and Limit Switch XA1.

Figure 7. Utility Restored, Transfer Relay De-energized.