beautypg.com

Appendix d.3. error codes – FieldServer FS-8704-14 User Manual

Page 30

background image

FS-8704-14 EtherNet/IP Manual

Page 30 of 31

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

Appendix D.3. Error Codes

General
Status

Extended
Status

Description

0x01

0x0100

Connection in Use or Duplicate Forward Open.

0x01

0x0103

Transport Class and Trigger combination not supported

0x01

0x0106

Ownership conflict

0x01

0x0107

Connection not found at target application.

0x01

0x0108

Invalid Connection Type. Indicates a problem with either the Connection Type or
Priority of the Connection.

0x01

0x0109

Invalid connection size

0x01

0110

Device not configured

0x01

0x0111

RPI not supported. May also indicate problem with connection time-out multiplier
or production inhibit time.

0x01

0x0113

Connection Manager cannot support any more connections

0x01

0x0114

Either the Vendor Id or the Product Code in the key segment did not match the
device

0x01

0x0115

Product Type in the key segment did not match the device

0x01

0x0116

Major or Minor Revision information in the key segment did not match the device

0x01

0x0117

Invalid Connection Point

0x01

0x0118

Invalid Configuration Format

0x01

0x0119

Connection request fails since there is no controlling connection currently open.

0x01

0x011A

Target Application cannot support any more connections

0x01

0x011B

RPI is smaller than the Production Inhibit Time

0x01

0x0203

Connection cannot be closed since the connection has timed out

0x01

0x0204

Unconnected Send timed out waiting for a response.

0x01

0x0205

Parameter Error in Unconnected Send Service

0x01

0x0206

Message too large for Unconnected message service

0x01

0x0207

Unconnected acknowledge without reply

0x01

0x0301

No buffer memory available

0x01

0x0302

Network Bandwidth not available for data

0x01

0x0303

No Tag filters available

0x01

0x0304

Not Configured to send real-time data

0x01

0x0311

Specified Port Not Available – the FieldServer is trying to open a connection but
the target port is not available at the remote device. This can be resolved by using
the correct EIP_Path parameter.

0x01

0x0312

Link Address specified in Port Segment Not Available

0x01

0x0315

Invalid Segment Type or Segment Value in Path

0x01

0x0316

Path and Connection not equal in close

0x01

0x0317

Either Segment not present or Encoded Value in Network Segment is invalid.

0x01

0x0318

Link Address to Self Invalid

0x01

0x0319

Resources on Secondary Unavailable

0x01

0x031A

Connection already established

0x01

0x031B

Direct connection already established

0x01

0x031C

Miscellaneous

0x01

0x031D

Redundant connection mismatch

0x01

0x031D

No more consumer resources available in the producing module

0x01

0x031E

No connection resources exist for target path

0x01

0x0320-

Vendor Specific