Error

Code

Maintenance

ICON

Problem

Control Board's Action

1

Flash

Front Panel Button Stuck For More
Than 20 Seconds

Continue to monitor for "OPEN" (Unstuck) switch. Do not process switch
input. ENSURE FRONT COVER DOES NOT DEPRESS BUTTONS

2

Flash

Input Voltage Out of Specification (103
- 127 / 187 - 253)

Stop.Open all relays until voltage is back within specs. Resume operation

3

Flash

Indoor Temperature Sensor is Open or
Shorted

Set temp to 75°F in COOLING or 68°F in HEATING. Unit continues to
operate

4

Flash

Indoor Coil Temperature Sensor is
Open or Shorted

Control Board sets temp to 40°F. Override sensor. Unit Continues to
operate.

5

Flash

Outdoor Coil Temperature Sensor is
Open or Shorted

Sets temp to 20°F. Override sensor. Continue operation. Use Elec Heat if
available for HEATING. If not available use HEAT PUMP if outdoor temp
allows.

6

Flash

Outdoor Coil > (grater than) 175 F

Shut down for 5 min. Resume operation for 3 min. Continues to monitor. If
test fails 3 times, the severity is increased and the unit operation is locked
out.

7

Flash

Indoor Coil < (less than) 30 F for 2
consecutive minutes

Turn compressor off. Run High Fan speed. When coil temp reachs 45°F
resume operation after lockout time.

8

Log Only

Unit Cycles > (grater than) 9 Times per
hour

Continue operation. Continue to monitor. Take no action. Log Only.

9

Log Only

Unit Cycles < (less than) 3 Times per
Hour

Continue operation. Continue to monitor. Take no action. Log Only.

10

Log Only

Room Freeze Protection

Only used if Electric Heat is available. Run High Speed and Electric heat
until room temp reaches 46°F. Display "FRZ" during operation. Logged
Only

11

On

WallStat Problem or Connection Issue

Severity 4 error is. Unit operates based on standard input mapping.
Severity 2 error opens all relays. Unit will not operate.

12

Flash

Discharge Air > (greater than) 185 F

Shutdown heat pump and electric heater. Run high fan speed until temp is
100°F. Resume operation. Third occurance in 1 hour locks unit out.

13

Flash

Prerssure Limit Switch Open

If unit is cooling or heat pump on,shut down compressor. Run high fan until
switch closes. Resume operation. Third occurance in 1 hour locks unit out.

14

Flash

Discharge Air Temperature Sensor is
Open or Shorted

Override Sensor. Set temp to 75°F. Continue to monitor. Set error code 14
ON.

15

Solid On

Heat Pump Error

If indoor coil temp < (Lesser than) ambient temp for 3 minutes. Unit uses
electric heat to satisfy heating demand.

16

Flash

Temperature Beyond Operating Limits

Ambient temp < (less than) 0°F and ambient temp > (greater than) 130°F.
Set error code 16 ON. When cleared return unit to normal.

17

Flash

Equipment Doesn't Meet Minimum
Configuration

Must have compressor enabled and at least 2 fan speeds

18

Flash

Special Test 1 Severity Level 1

Unit shuts down. Inputs via front panel or t-stat are ignored. Qualified
Technical Service required URGENT

19

Flash

Special Test 2 Severity Level 2

Unit operates. Qualified Technical Service required

20

Solid On

Special Test 3 Severity Level 3

Error is Logged Only. Unit operates. Severity 3 keeps unit running.
Attention is needed

21

OFF, Log Only Special Test 4 Severity Level 4

Error is Logged Only. Unit operates. Severity 4 keeps unit running.

22

OFF, Log Only

Outdoor Coil Temperature < 30 F for 2
consecutive Minutes

Unit will use electric heat to satisfy heating demands until temp > 45°F.
Unit must be a Heat Pump.

23

OFF, Log Only

Frost Protection (for Heat Pump Only
Unit- YS10M10)

Unit will run active defrost for a minimum of 6 minutes when Heat Pump
run time is greater than 60 minutes and outdoor coil temp is 26 F or less.

24

Flash

Outdoor Air Temperature Sensor is
Open or Shorted

Continue with normal operation. Continue to monitor sensor.

Key Sequence

Action

Enter Maintenance Menu

Press SYSTEM + SCHEDULE + BACK + DISPLAY/ENTER for 6 secs or until double beep sounds()

Reset Error Codes & Error History Press

+

for 3 secs or until double beep sounds ( )

ERROR CODES AND ALARM STATUS