ELECTRONIC CONTROL SEQUENCE OF OPERATION
Compressor and Reversing Valve Control
Cooling
De-Energized
Energized
On
On
Off
Off
Heat - Heat Pump
Heat - Electric
Fan Only
* The Reversing valve stays in the last state until a call for heat or cooling (see fi gure below)
Compressor Operation:
Cooling Mode
Once the ambient temperature rises past the cool demand threshold (Cool Set Point + 1.5 ˚F) (see fi gure below), and
the compressor is not locked out, the cooling cycle begins. As shown in the fi gure below, the fan is started 5 seconds
prior to the compressor. Once the ambient temperature has been lowered to the cool set point (Cool Set Point minus
.25 ˚F), the cooling cycle starts to terminate by shutting off the compressor. After a 30 seconds delay, the fan is shut
off. (See fi gure below for graphic details)
The reversing valve only changes when required
to provide cooling or heat pump. The RV valve
stays in it's last state until required to change.
Active Mode
Compressor
Reversing Valve State
- Kuhl Series 12000 BTU Smart Window Air Conditioner Warranty (43 pages)
- Kuhl Series 12000 BTU Smart Window Air Conditioner Warranty (16 pages)
- Kuhl Series 23,000 BTU Smart Window Wall Room Air Conditioner Warranty (54 pages)
- Kuhl Series 12000 BTU Smart Window Air Conditioner Warranty (56 pages)
- Kuhl Series 12000 BTU Smart Window Air Conditioner Warranty (43 pages)
- Kuhl Series 12000 BTU Smart Window Air Conditioner Warranty (58 pages)
- Kuhl Series 12000 BTU Smart Window Air Conditioner Warranty (59 pages)
- Kuhl Series 12000 BTU Smart Window Air Conditioner Warranty (24 pages)
- Kuhl Series 12000 BTU Smart Window Air Conditioner Warranty (62 pages)
- CP08E10 (30 pages)
- ZoneAire Series 42 Inch Packaged Terminal Air Conditioner Warranty Guide (56 pages)
- ZoneAire Series 42 Inch Packaged Terminal Air Conditioner Warranty Guide (28 pages)
- ZoneAire Series 14,500 BTU Smart Packaged Terminal Air Conditioner Installation Guide (36 pages)
- ZoneAire Series 42 Inch Packaged Terminal Air Conditioner Warranty Guide (72 pages)
- P/N9368987060-01 (18 pages)
- CP08F10 (29 pages)
- ES12 (56 pages)
- Hazardgard Series 19,000 BTU Commercial Room Air Conditioner Warranty (16 pages)
- Hazardgard Series 19,000 BTU Commercial Room Air Conditioner Warranty (16 pages)
- MR09C1H (28 pages)
- HEAT&COOLING MODEL INVERTER (REVERSE CYCLE) ROOM AIR CONDITIONER WALL MOUNTED TYPE (50 pages)
- MW18Y3H (28 pages)
- 2009 (44 pages)
- CP10F10 (28 pages)
- MR24Y3F (24 pages)
- 1883 (2 pages)
- CP24 (16 pages)
- A Series / 24 (8 pages)
- M36CF (2 pages)
- PDXDEA (5 pages)
- P12A (12 pages)
- MR12C1F (17 pages)
- MS36Y3F (25 pages)
- 115 Volts US10 (61 pages)
- P12B (12 pages)
- EQ08L11A (2 pages)
- ES12M33 (132 pages)
- KP05A10 KP06A10 (27 pages)
- MW24Y3H (52 pages)
- CP05 CP Line (43 pages)
- CP06/CP08 (59 pages)
- MW18C3F (50 pages)
- MR36C3F (24 pages)
- ZQ08A10C (28 pages)
- KS10 (24 pages)