Heating mode control operation, Heat control operation heat pump only – Friedrich KUHL R-410A User Manual
Page 25

24
Heat Control (Heat Pump Only)
Heating Mode Control Operation
There are two heating methods: Heat Pump and Electric Resistance Heat.
There are 3 types of units that provide heating: Heat Pump Only (Model YS10M10)
Heat Pump with Electric Heat and Cool with Electric Heat.
Heat Control Operation Heat Pump Only
Once the ambient temperature falls below the Heating Demand Threshold
(1.5 ˚F Below the Heat Set Point Temperature), the heating cycle begins. The fan is turned on 5 seconds later. Once
the ambient temperature has been raised to the Heat Satisfi ed Point (Set point + .25 ˚F), the compressor is turned
off. The fan is turned off 30 seconds later. The fi gure below illustrates the basic heat pump operation.
See also other documents in the category Friedrich Conditioners:
- Kuhl Series 12000 BTU Smart Window Air Conditioner Warranty (43 pages)
- Kuhl Series 12000 BTU Smart Window Air Conditioner Warranty (16 pages)
- Kuhl Series 23,000 BTU Smart Window Wall Room Air Conditioner Warranty (54 pages)
- Kuhl Series 12000 BTU Smart Window Air Conditioner Warranty (56 pages)
- Kuhl Series 12000 BTU Smart Window Air Conditioner Warranty (43 pages)
- Kuhl Series 12000 BTU Smart Window Air Conditioner Warranty (58 pages)
- Kuhl Series 12000 BTU Smart Window Air Conditioner Warranty (59 pages)
- Kuhl Series 12000 BTU Smart Window Air Conditioner Warranty (24 pages)
- Kuhl Series 12000 BTU Smart Window Air Conditioner Warranty (62 pages)
- CP08E10 (30 pages)
- ZoneAire Series 42 Inch Packaged Terminal Air Conditioner Warranty Guide (56 pages)
- ZoneAire Series 42 Inch Packaged Terminal Air Conditioner Warranty Guide (28 pages)
- ZoneAire Series 14,500 BTU Smart Packaged Terminal Air Conditioner Installation Guide (36 pages)
- ZoneAire Series 42 Inch Packaged Terminal Air Conditioner Warranty Guide (72 pages)
- P/N9368987060-01 (18 pages)
- CP08F10 (29 pages)
- ES12 (56 pages)
- Hazardgard Series 19,000 BTU Commercial Room Air Conditioner Warranty (16 pages)
- Hazardgard Series 19,000 BTU Commercial Room Air Conditioner Warranty (16 pages)
- MR09C1H (28 pages)
- HEAT&COOLING MODEL INVERTER (REVERSE CYCLE) ROOM AIR CONDITIONER WALL MOUNTED TYPE (50 pages)
- MW18Y3H (28 pages)
- 2009 (44 pages)
- CP10F10 (28 pages)
- MR24Y3F (24 pages)
- 1883 (2 pages)
- CP24 (16 pages)
- A Series / 24 (8 pages)
- M36CF (2 pages)
- PDXDEA (5 pages)
- P12A (12 pages)
- MR12C1F (17 pages)
- MS36Y3F (25 pages)
- 115 Volts US10 (61 pages)
- P12B (12 pages)
- EQ08L11A (2 pages)
- ES12M33 (132 pages)
- KP05A10 KP06A10 (27 pages)
- MW24Y3H (52 pages)
- CP05 CP Line (43 pages)
- CP06/CP08 (59 pages)
- MW18C3F (50 pages)
- MR36C3F (24 pages)
- ZQ08A10C (28 pages)
- KS10 (24 pages)