Power supply, Measurement – Fluke 1744 User Manual
Page 58
![background image](/manuals/103148/58/background.png)
Power Quality Logger
Technical
Specifications
49
Power Supply
Functional range
88 to 660 V RMS ac absolute, 50 Hz / 60 Hz
Safety
EN 61010-1 600 V CAT III, 300 V CAT IV,
pollution degree 2, double insulation
Fuse
Power supply fuse can be replaced only in service
facility. Supply can be connected in parallel to
measuring inputs (up to 660 V RMS ac).
Power consumption
5 W
Memory capacity
8 MB Flash-EPROM
Intervals
> 5.600 intervals, > 39 days with 10-min intervals
Events >
13.000
Memory model
Linear, circular
Interface
RS232, 9600 to 115000 Baud, automatic selection,
3-wire communication.
Dimensions
170 mm x 125 mm x 55 mm
Weight
Approx. 0.9 kg
Measurement
A/D converter
16 bit
Sampling frequency
10.24 kHz
Anti-aliasing filter
FIR-Filter, f
C
= 4.9 kHz
Frequency response
Uncertainty < 1% of Vm for 40 to 2500 Hz
Interval length
1, 3, 5, 10, or 30 seconds,
1, 5, 10, 15, or 60 minutes
Averaging time for
min/max values
½ , 1 line power period
200 ms
1, 3, 5 s
Time base
Resolution: 10 ms (at 50 Hz) deviation: 2 s/day
at 23 °C.