Calculation of thd in measuring function p, Flicker, Vthdv – Fluke 1744 User Manual

Page 44: Ithdi

background image

Power Quality Logger

Methods of Logging

35

Calculation of THD in Measuring Function P

THD – Measuring Function P

Function P does not measure harmonic values.

Voltages:

1

2

1

2

V

V

V

THDV

RMS

=

V

RMS

: RMS value of total signal

V

1

: RMS value of the fundamental

Currents:

1

2

1

2

I

I

I

THDI

RMS

=

I

RMS

: RMS value of the total signal.

I

1

: RMS value of the fundamental.

Note

THDI for currents < 5% of IE (measuring range) can have additional
uncertainties, or can be suppressed.

Harmonics up to 50th order are taken into account.

Flicker

Flicker is the visual impression of unsteadiness in a light source whose
luminance or spectral distribution changes over time. Flicker is logged in
accordance with the IEC 61000-4-15 standard. The short-term (st) flicker Pst

t

is logged over a default standard interval of 10 minutes, and is used to
calculate the long-term (lt) flicker Plt (by taking the sliding average of 12
short-term values). The interval value can be changed as needed in PQ Log.