Power Quality Logger

Logger Parameters with Function P

39

P

k

: Active power of the phase

k: Phase (k = 1, 2, 3)

Absolute value of the active power
per interval per phase. Parameter in
PQ Log: |P|.

=

=

M

j

j

bas

betr

P

M

P

1

1

M: Number of 200 ms intervals per

logging interval

Sum of the absolute value of the total
active power on all three phases. PQ
Log parameter: |P|

total

.

( )

k

k

betr

betrtotal

P

P

=

=

3

1

K: Phase (k = 1, 2, 3)

Apparent power per phase

2

2

bas

bas

bas

Q

P

S

+

=

Apparent power per logging interval
per phase

=

=

M

j

j

bas

S

M

S

1

1

Total apparent power on all three
phases

=

=

3

1

k

k

total

S

S

Power factor per phase

S

P

Q

Q

PF

=

=

λ

Total power factor on all three
phases

total

total

total

total

total

total

Q

Q

S

P

PF

=

=

λ

Tangent φ per phase

P

Q

=

ϕ

tan