Unbalance, Frequency, Formula for plt function – Fluke 1744 User Manual

Page 45: Pst plt

background image

1744/1743

Users Manual

36

Formula for Plt Function

3

12

1

3

12

=

=

i

Pst

Plt

Time

Flicker [%]

Interval length => 1 Pst

12 x interval length => 1 flicker value Plt

egb020.eps

Figure 17. Measuring Flicker Values

Unbalance

The ratio of negative-to-positive sequence harmonics is calculated, with the
angles and magnitudes of the phase voltages taken into account. These values
are averaged over the interval length defined in PQ Log.

Frequency

The line power frequency is measured and averaged over 10 seconds, and the
resulting values are divided into 42 classes for establishing statistics. Values
are also averaged over the interval length defined in PQ Log.