Fluke 434 User Manual
Page 108

Fluke 433/434
Users Manual
21-6
Measurements Measurement
Range Resolution
Accuracy
RMS voltage in Transient
Function
10 ... 1000 Vrms
1 Vrms
± 2.5 % of Vnom
Transient voltage
(TTRANS > 10 µs)
0 ... ± 6000 Vpeak
1 V
± 15 % of meas
Flicker
Settings Adjustment
Range
Resolution
Additional
Information
Steady Voltage
Tolerance
0.0 ... 10.0 % of Vnom
0.1 %
Minimum Steady Time
0.0 ... 10.0 s
0.1 s
Maximum Deviation
Threshold
0.0 ... 10.0 % of Vnom
0.1 %
Measurement Measurement
Range Resolution
Accuracy
PF5
0.00 ... 20.00
0.01
P1min
0.00 ... 20.00
0.01
Pst
0.00 ... 20.00
0.01
Plt
0.00 ... 20.00
0.01
Within ±5 % of tabulated
values according
IEC61000-4-15
Dc
0.0 ... ± 100.0 %
0.1 %
± 1 % (if Umeas
≈ Vnom)
DMAX
0.0 ... ± 100.0 %
0.1 %
± 1 % (if Umeas
≈ Vnom)
TDEX
0.000 ... 9.999 s
10 ms
20 ms (at F = 50 Hz)
CURRENT MEASUREMENTS
Current Inputs
Item Specification
Additional
Information
Nominal input Range
0 - ±5.625 Vpeak
0 - 3.97 Vrms sinewave
Current Clamp Sensitivity
0.1 , 1, 10, 100, 1000 mV/A
variable:
Input impedance
50 k.ohm
Bandwidth >10
kHz
Voltage resolution
1 mV