Fault class 8:
NC Editor, Upload/download or operation execution fault
Fault
stage
Fault
message
Operating status / fault explanation
Eliminating faults
D
nnn01x08
ppp01x08
Syntax fault or non−permitted program
number entered
·
Correct entry
ppp02x08
When using the control panel:
Ĉ Non−permitted program number selected,
program cannot be created as it already
exists or program cannot be opened as it
does not exist.
Ĉ No free memory space
When using WinPISA:
Ĉ Program could not be loaded When the
fault is deleted, the memory of the SPC200
will be re−assigned.
·
Correct entry
If the maximum number of NC
records is not yet reached:
·
Carry out program modificaĆ
tion with WinPISA; if necessĆ
ary the memory will be
re−assigned.
·
Load the program again
when the memory has been
re−assigned.
nnn03x08
Non−permitted record number
·
Correct entry
ppp04x08 No free memory space for new program
·
Delete unnecessary
programs and NC records
ppp05x08
Test sum fault
·
Servicing required
00006x08
to
0000Ax08
Fault in Upload/Download with WinPISA
·
Check connecting cable and
diagnostic module; if necessĆ
ary set lower baud rate
0000Bx08 Enable signal missing
·
Apply a 1−signal at the
ENABLE input
0000Cx08
System has stopped, there is a 0−signal at
the STOP input
·
Apply a 1−signal at the STOP
input
0000Dx08 Starting program does not exist
·
Correct the number of the
starting program
0000Ex08
Command not permitted in this operating
mode
·
Do not use this command in
the current operating mode
or modify the operating mode
zzz = Additional information
yy = Fault number
x
= Axis identifier (0 = fault is not axis−related)
ppp = Program number
nnn = NC record number of the accessing NC command