1-74

1. Specifications

4. HOW TO INSTALL THE OUTDOOR UNIT

4-1. Installing the Outdoor Unit

Use concrete or a similar material to create the base,

and ensure good drainage.

Ordinarily, ensure a base height of 2". or more. If a

drain pipe is used, or for use in cold-weather regions,
ensure a height of 6". or more at the feet on both sides
of the unit. (In this case, leave clearance below the unit
for the drain pipe, and to prevent freezing of drainage
water in cold-weather regions.)

Refer to the Fig. 1-10 for the anchor bolt dimensions.

Be sure to anchor the feet with the anchor bolts (M10).

In addition, use anchoring washers on the top side. (Use
large square 32×32 SUS washers with diameters of
10.) (Field supply)

4-2. Drainage Work

Follow the procedure below to ensure adequate draining
for the outdoor unit.

For the drain port dimensions, refer to the fi gure at

right.

Ensure a base height of 6 in. or more at the feet on

both sides of the unit.

4-3. Routing the Tubing and Wiring

The tubing and wiring can be extended out in 4

directions: front, rear, right, and down.

The service valves are housed inside the unit. To

access them, remove the inspection panel. (To remove
the inspection panel, remove the 3 screws, then slide
the panel downward and pull it toward you.)

(1) If the routing direction is through the front, rear,

or right, use a nipper or similar tool to cut out the
knockout holes for the inter-unit control wiring outlet,
power wiring outlet, and tubing outlet from the
appropriate covers A and B.

(2) If the routing direction is down, use a nipper or similar

tool to cut out the lower fl ange from cover A.

CAUTION

Route the tubing so that it does

not contact the compressor,
panel, or other parts inside the
unit. Increased noise will result if
the tubing contacts these parts.

When routing the tubing, use a

tube bender to bend the tubes.

Fig. 1-10

Fig. 1-11

37-1/64

11-21/32

5-29/32

8-5/8

33/64

33/64

25/32

25/32

19/32

25/64

14-61/64

15-15/16

13-25/64

33/64

33/64

6-11/16

4-21/64

25-63/64

Drain port (2 locations)

Drain port

Anchor bolt (M10)

Unit: inch

Inter-unit control wiring outlet

Inspection panel

Cover A

Cover B

Power wiring outlet

Tubing outlet

Down

Front

Rear

Right

1

SM830203-01_PAC-i_US-letter.indb74 74

SM830203-01_PAC-i_US-letter.indb74 74

2012/01/19 22:39:29

2012/01/19 22:39:29