beautypg.com

Service procedures – Panasonic 36PSU1U6 User Manual

Page 171

background image

4-7

4. Service procedures

Judgment condition

Clear condition

F31

L02

L04

L07

L10

L13

E07

E06

E14

E15

E16

E20

E31

H01

Remote

controller

alarm display

Alarm

contents

Judgment and correction

Automatic recovery

EEPROM trouble

Reading/writing failure

Recovery at power
reset

1. Check EEPROM (IC007).
2. Check outdoor unit control

PCB.

Mismatch of indoor
and outdoor unit types
(Espacio, Multi )

Indoor unit judges that type
does not match outdoor unit
type.

Recovery at power
reset

1. Check indoor unit EEPROM.
2. Check indoor unit control

PCB.

Settings failure

Settings failure

Settings failure

Duplicated outdoor unit
address (system address)

1. Check outdoor unit

system address.

2. Check inter-unit control

wiring.

Group control wiring is
connected to an
independent-control indoor

Recovery at power
reset

1. Check inter-unit control

wiring.

2. Check indoor unit

EEPROM.

Outdoor unit capacity not set.

Recovery at power
reset

Check outdoor unit EEPROM.

Indoor-outdoor unit
types

Outdoor unit judges that type
does not match indoor unit
type.

Recovery at power
reset

1. Check indoor unit

EEPROM.

2. Check outdoor unit control

PCB.

Outdoor unit detected
abnormal signal from
indoor unit.

Serial signal receiving failure
(including failure to verify No.
of units)

Automatic
recovery

Automatic
recovery

1. Check inter-unit control

wiring.

2. Check outdoor unit

Outdoor unit sending
failure to indoor unit

l

o

r

t

n

o

c

t

i

n

u

-

r

e

t

n

i

k

c

e

h

C

.

1

e

r

u

li

a

f

g

n

i

d

n

e

s

l

a

n

g

i

s

l

a

i

r

e

S

wiring.

2. Check outdoor unit control

PCB.

Settings failure

Duplicated master unit in
simultaneous-operation multi
control
(Detected by outdoor unit)

Recovery at power
reset

1. Check inter-unit control

wiring.

2. Check indoor unit

combination.

Automatic address
setting failure

Automatic address
setting failure

Automatic address
setting failure

Indoor unit capacity too low.

Recovery at power
reset

Recovery at power
reset

Recovery at power
reset

1. Check inter-unit control

wiring.

2. Check outdoor unit control

PCB.

l

o

r

t

n

o

c

t

i

n

u

-

r

e

t

n

i

k

c

e

h

C

.

1

.

h

g

i

h

o

o

t

y

t

i

c

a

p

a

c

t

i

n

u

r

o

o

d

n

I

wiring.

2. Check outdoor unit control

PCB.

Outdoor unit cannot receive
any serial signals from indoor
units.

1. Check inter-unit control

wiring.

2. Check outdoor unit control

PCB.

Communications
trouble within unit

No communication possible
with MDC for 3 minutes or
longer.

Automatic recovery Check outdoor unit control

PCB.

Overcurrent

Inverter stops after alarm is
detected.

Recovery at restart

1. Refrigerant cycle trouble,

overload operation

2. Loose screws between HIC

control PCB and radiating
plate

3. Cooling failure of radiating

plate

4. Check outdoor unit PCB

wiring.

4

SM830203-01_PAC-i_US-letter.indb7 7

SM830203-01_PAC-i_US-letter.indb7 7

2012/01/26 10:32:03

2012/01/26 10:32:03