beautypg.com

Specifications – Panasonic 36PSU1U6 User Manual

Page 129

background image

1-123

1. Specifications

(3) Pressurize the system up to 4.15 MPa

(42 kgf/cm

2

G) with dry nitrogen gas and close the

cylinder valve when the gauge reading reaches
4.15 MPa (42 kgf/cm

2

G). Then, test for leaks with

liquid soap.

CAUTION

To avoid nitrogen entering the
refrigerant system in a liquid
state, the top of the cylinder
must be higher than the bottom
when you pressurize the
system. Usually, the cylinder is
used in a vertical standing
position.

Fig. 1-125

CAUTION

Use a cylinder specifi cally
designed for use with R410A.

(4) Do a leak test of all joints of the tubing (both

indoor and outdoor) and both gas and liquid
service valves. Bubbles indicate a leak. Wipe
off the soap with a clean cloth after the leak test.

(5) After the system is found to be free of leaks,

relieve the nitrogen pressure by loosening the
charge hose connector at the nitrogen cylinder.
When the system pressure is reduced to normal,
disconnect the hose from the cylinder.

2. Evacuation

Be sure to use a vacuum pump that includes a
function for prevention of back-fl ow, in order to
prevent back-fl ow of pump oil into the unit tubing
when the pump is stopped.

Perform vacuuming of the indoor unit and tubing.

Connect the vacuum pump to the gas tube valve
and apply vacuum at a pressure of –101kPa ( –755
mmHg, 5 Torr) or below.
Continue vacuum application for a minimum of 1
hour after the pressure reaches –101kPa ( –755
mmHg, 5 Torr).

(1) Attach the charge hose end described in the

preceding steps to the vacuum pump to evacuate
the tubing and indoor unit. Confi rm that the “Lo”
knob of the manifold valve is open. Then, run the
vacuum pump.

(2) When the desired vacuum is reached, close the

“Lo” knob of the manifold valve and turn off the
vacuum pump. Confi rm that the gauge pressure is
under –101kPa ( –755 mmHg, 5 Torr) after 4 to 5
minutes of vacuum pump operation.

Manifold valve

Pressure
gauge

Lo

Hi

Vacuum pump

Outdoor unit

Liquid
tube

Gas
tube

Close

Close

Open

1

SM830203-01_PAC-i_US-letter.indb123 123

SM830203-01_PAC-i_US-letter.indb123 123

2012/01/19 22:39:36

2012/01/19 22:39:36