beautypg.com

3. details of alarm messages, Service procedures – Panasonic 36PSU1U6 User Manual

Page 172

background image

4-8

4. Service procedures

No

No

No

No

No

No

No

No

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

[Alarm “P29”]
(MDC trouble)

(1)

Input power detection circuit trouble

Compressor does not run.

Breakdown

Motor current detection circuit trouble

Is power OK?

Correct power line.

Is

current

detection

circuit wiring

OK?

Check and correct
wiring.

Are

wiring and

connector

connections

OK?

Check and correct
wiring.

Is

compressor

OK?

Ground

fault?

Replace

compressor.

Coil

resistor

short circuit?

Coil open

circuit?

Is there

abnormal refrigerant

accumulation?

Replace

compressor.

Is

operation of

electronic

control valve

OK?

Replace outdoor

unit control PCB.

Are

C1 and TS

sensors

OK?

Replace C1 and

TS sensors.

Replace electronic

control valve.

Is there overload?

Remove

the cause.

4-3. Details of Alarm Messages

4

SM830203-01_PAC-i_US-letter.indb8 8

SM830203-01_PAC-i_US-letter.indb8 8

2012/01/26 10:32:04

2012/01/26 10:32:04