beautypg.com

1. meaning of alarm messages, Service procedures – Panasonic 36PSU1U6 User Manual

Page 166

background image

4-2

4. Service procedures

Remote controller is
detecting error signal from
indoor unit

E01

E02

E10

E11

E14

E03

E08

E09

E04

E05

E06

E07

E15

E12

E16

E20

E17

E18

E31

L01

L02

L03

L04

L07

L08

L09

L10

L11

L13

Indoor unit is detecting error signal from remote controller (and system controller)

Error in receiving serial communication signal
(Signal from main indoor unit in case of group control)

Auto address is not completed

Outdoor system address, indoor system address, or indoor unit
individual/main/sub setting is not set
(Automatic address setting is not completed)

Error in transmitting serial communication signal

Improper setting of indoor
unit or remote controller

Indoor unit address setting is duplicated

Remote controller setting is duplicated

Error in transmitting serial communications signal

Error in transmitting serial communications signal

Error in receiving serial communications signal

Error in receiving serial communications signal

Indoor unit is detecting error
signaled from signal option

Setting error

Main unit duplication in simultaneous-operation multi control
(detected by outdoor unit)

Indoor unit is detecting error
signaled from outdoor unit

Outdoor unit is detecting
error signaled from indoor
unit

Automatic address setting
failed

An indoor unit detected
trouble in the signal from
another indoor unit

Communications trouble
between units

Setting error

Mis-setting

Continued

Error in transmitting serial communications signal

I

Starting auto address setting is prohibited
This alarm message shows that the auto address connector
CN100 is shorted while other RC line is executing auto address
operation.

ndoor unit capacity too low

Indoor unit capacity too high

No indoor units connected

Error in receiving serial communications signal

Communications failure with MDC

Indoor unit group settings error

Indoor/outdoor unit type mismatch

Main unit duplication in group control (detected by indoor unit)

Outdoor unit address duplication (system address)

Group wiring connected for independent indoor unit

Address not set or group not set

Indoor unit capacity not set

Outdoor unit capacity not set or setting error

Miswiring in group control wiring

Indoor unit type setting error (capacity)

Error in transmitting serial communications signal

Error in receiving serial communications signal (including unit
quantity verification failure)

Simultaneously

Simultaneously

Simultaneously

Simultaneously

Serial commu-
nication errors
Mis-setting

Wired

remote
control

display

Wireless

remote controller

receiver display

ON:

Operation

Timer

S

tandb

y

Blinking:

OFF:

Possible cause of malfunction

4-1. Meaning of Alarm Messages

(1) Contents of remote controller switch alarm display

4

SM830203-01_PAC-i_US-letter.indb2 2

SM830203-01_PAC-i_US-letter.indb2 2

2012/01/26 10:32:03

2012/01/26 10:32:03