1-65

1. Specifications

3. SELECTING THE INSTALLATION SITE

3-1. Outdoor Unit

AVOID:

heat sources, exhaust fans, etc. (Fig. 1-3)

damp, humid or uneven locations

DO:

choose a place as cool as possible.

choose a place that is well ventilated and outside

air temperature does not exceed maximum 115°F
constantly.

allow enough room around the unit for air intake/
exhaust and possible maintenance. (Fig. 1-4)

use lug bolts or equal to bolt down unit, reducing

vibration and noise.

if cooling operation is to be used when the outdoor air
temperature is 23°F or below, install a duct on
the outdoor unit.

Installation space

Distance between obstructions and the unit air inlet
and outlet must be as shown below.

Installation requirements

provide a solid base (concrete block, 4"×16"
beams or equal), a minimum of 6" above ground
level to reduce humidity and protect the unit against
possible water damage and decreased service life.
(Fig. 1-6)

use lug bolts or equal to bolt down unit, reducing
vibration and noise.

Fig. 1-5

Out-
door
unit

Heat source

Hot air

Exhaust fan

*4

*2

*3

*1

More than 1/2"

More than
3.3 ft.

More than 1/2"

Inlet side C

Outlet side

*1

Inlet side
More than 8"

(field supply)

A

B

(Ground)

Air direction chamber

(Obstruction above unit)

(Obstruction on
inlet side)

Anchor bolts
(4 pieces)

Fig. 1-4

Fig. 1-3

Fig. 1-6

CAUTION

Concerning inlet-side distance “C” (Fig. 1-4)
The minimum for distance “C” is 6" if there are no obstructions on the outlet side
(wall *1 side) and *2 or *4 is not present. In all other cases, the minimum for distance
“C” is 8".

If the unit is installed with the outlet side facing wall *1, then there must be no obstructions

on 2 of the remaining 3 sides: *2, *3, *4.
If wall *1 is on the outlet side (Fig. 1-4), or if obstructions are present on all 3 sides *2,
*3, and *4 (Fig. 1-4), then the minimum distance for “A” and “B” is 80" (Fig. 1-5). Even
if there is no wall on the outlet side, a minimum of 3.3 ft. is required.

1

SM830203-01_PAC-i_US-letter.indb65 65

SM830203-01_PAC-i_US-letter.indb65 65

2012/01/19 22:39:28

2012/01/19 22:39:28