HT instruments SPEED418 User Manual
Page 66
400
Series
EN - 65
Tripping current ( )
IdN [mA]
Type
Range IdN [mA]
Resolution [mA]
Uncertainty
≤ 10
AC
(0.5
1.1) IdN
0.1IdN -0%,
+10%rdg
A
(0.3
1.1) IdN
> 10
AC
(0.5
1.1) IdN
A
(0.3
1.1) IdN
RCD type
AC (
), A (
), general and selective
Tripping time
resolution 1ms,
uncertainty
(2.0%rdg + 2dgt)
Earth resistance (Ra)
Range [
] Resolution
[
]
Uncertainty
1
1999
1
(5.0rdg + 3dgt)
RCD type
AC (
), A (
), general and selective
Test current
< ½ IdN,
uncertainty: -10%, +0% IdN
Contact voltage Ut
range: 0
2Ut lim
resolution: 0.1V
uncertainty: -0%, +(5%rdg + 3dgt)
Line impedance and fault loop impedance (LOOP)
Phase-neutral and phase-earth voltage range
(110
240V) 10%
Phase-phase voltage range
(110
415V) 10%
Frequency 50Hz
0.5Hz, 60Hz 0.5Hz
TT and TN systems
Range [
] Resolution
[
]
Uncertainty
0.01
9.99
0.01
(5.0rdg + 3dgt)
10.0
199.9
0.1
200
1999 (phase-earth only)
1
Max peak test current at test voltage
3A @ 127V, 6A @ 230V, 10A @ 400V
IT systems
Range [mA]
Resolution [mA]
Uncertainty
5
999
1
(5.0rdg + 3dgt)
Contact voltage (ULIM)
25V, 50V
Total earth resistance (Ra)
Range [
] Resolution
[
]
Uncertainty
0.01
9.99
0.01
(5.0rdg + 1)
10.0
199.9
0.1
200
1999 (phase-earth only)
1
Test current
<15mA
Contact voltage (ULIM)
25V, 50V
Phase-neutral and phase-earth voltage range
(110
240V) 10%
Frequency 50Hz
0.5Hz, 60Hz 0.5Hz
Phas sequence (123)
Phase-neutral and phase-earth voltage range
(110
240V) 10%
Frequency 50Hz
0.5Hz, 60Hz 0.5Hz
Leakage current (LEAK)
Range [mV]
Resolution [mV]
Uncertainty
1
1200.0
0.1
(1.0rdg + 2dgt)
Max crest factor
3
Response time
10ms
Frequency 50Hz
0.5Hz, 60Hz 0.5Hz