97ms, 27ma, 42ma – HT instruments SPEED418 User Manual
Page 33: 400 series, En - 32

400
Series
EN - 32
4. If the selective RCD trips in a
time lower than the minimum 
limit reported in Tab. 5, the 
instrument gives a long 
acoustic signal which signals 
the negative result of the test 
and then displays a screen 
similar to the one reported 
here to the side. Check that 
the set type of RCD matches 
the type of RCD being tested
R C D
0°
97ms
FRQ=50.0Hz
Ut=1.4V
VP-N=221V
VP-Pe=221V
TIME NOT OK
The tripping time is not compliant 
with Tab. 5 
x1 30mA S
50V
Func
IdN RCD UL
5. If, during a test in mode,
the RCD trips in a time 
exceeding the maximum 
duration time provided for 
the test, the instrument gives 
a long acoustic signal which 
signals the negative result of 
the test and then displays a 
screen similar to the one 
reported here to the side
R C D
0°
27mA
>
3 0 0 m s
FRQ=50.0Hz
Ut=1.4V
VP-N=228V
VP-Pe=228V
The tripping time is not conform
TIME NOT OK
30mA
50V
Func
IdN RCD UL
6. If, during a test in mode,
the RCD does not trip, the 
instrument gives a long 
acoustic signal which signals 
the negative result of the test 
and then displays a screen 
similar to the one reported 
here to the side
R C D
0°
> 42mA
>
3 0 0 m s
FRQ=50.0Hz
Ut=1.4V
VP-N=228V
VP-Pe=228V
The tripping time is not conform
CURRENT NOT OK
30mA
50V
Func
IdN RCD UL
7.
The results displayed can be saved by pressing the SAVE key twice or the 
SAVE
key and, subsequently, the ENTER key (§ 9.1)
8. If the instrument detects that
the phase and neutral leads 
are inverted, the message 
reported here to the side is 
displayed. Rotate the shuko 
plug or check the connection 
of the single cables
R C D
0°
---ms
FRQ=50.0Hz
Ut=1.4V
VP-N=228V
VP-Pe= 1V
REVERSE P-N
The phase and neutral conductors 
are inverted 
x1 30mA
50V
Func
IdN RCD UL
