400

Series

EN - 31

6. After the test is completed, if

the measured resistance
value matches the nominal
current and the set limit
contact voltage, RA

    (1666Ω @ UL=50V and
    IdN=30mA), the instrument
    gives a double acoustic
    signal and displays the
    message “OK”, which

    R C D

    39

    FRQ=50.0Hz

    Ut=1.4V

    VP-N=228V

    VP-Pe=228V

    Value of total earth resistance

    Detected value for contact voltage Ut
    compared to the nominal value of
    the set residual current

    OK

    RA 30mA

    50V

    Func

    IdN RCD UL

    signals that the test has been completed successfully, and displays a screen similar to
    the one reported here to the side

    7.

    The results displayed can be saved by pressing the SAVE key twice or the
    SAVE

    key and, subsequently, the ENTER key (§ 9.1)


    6.4.6. Description of anomalous results

    1. By using the RA mode, if the

    instrument detects a contact
    voltage higher than the set
    limit, it displays the message
    reported here to the side.
    Check the efficiency of the
    protective conductor and the
    earthing

    R C D

    39

    FRQ=50.0Hz

    Ut=58.4V

    VP-N=228V

    VP-Pe=228V

    Dangerous contact voltage

    NOT OK

    RA 30mA

    50V

    Func

    IdN RCD UL

    2. If the RCD trips in a time

    exceeding the limits reported
    in Tab. 5, the instrument
    gives a long acoustic signal
    which signals the negative
    result of the test and then
    displays a screen similar to
    the one reported here to the
    side. Check that the set type
    of RCD matches the type of
    RCD being tested

    R C D

    487ms

    FRQ=50.0Hz

    Ut=1.4V

    VP-N=221V

    VP-Pe=221V

    TIME NOT OK

    The tripping time is not compliant
    with Tab. 5

    x1 30mA

    50V

    Func

    IdN RCD UL

    3. If the RCD does not trip

    within the maximum duration
    of the test, the instrument
    gives a long acoustic signal
    which signals the negative
    result of the test and then
    displays a screen similar to
    the one reported here to the
    side. Check that the set type
    of RCD matches the type of
    RCD being tested

    R C D

    >999ms

    FRQ=50.0Hz

    Ut=1.4V

    VP-N=221V

    VP-Pe=221V

    TIME NOT OK

    The RCD did not trip within the
    maximum duration of the test

    x1 30mA

    50V

    Func

    IdN RCD UL