Appendix, 1 command reference, 1 general parameter settings – Infinite Peripherals SCOM-100 User Manual
Page 30: 2 user configuration

SCOM-100, User guide
30
8. Appendix
8.1 Command reference
8.1.1 General parameter settings
Cmd
Description
Syntax
Comments
0000
Set Unit Mode: Stop
cmd
0100
Set Unit Mode: Control
cmd
0110
Set Unit Mode: Monitor
cmd
0150
Get Last Error Report
cmd
0171
Reset Device
cmd
0183
Set Factory Defaults
cmd,cmd
0200
Clear Error Led
cmd
0300
Set Device Name
cmd,s
s:0-15
0310
Set Device Description
cmd,s
s:0-60
0600
Set Remaining SMS Alarm Limit
cmd,l
l:0-4294967295
0601
Cancel Remaining SMS Alarm
cmd
0610
Set Verbose Responses
cmd
0611
Cancel Verbose Responses
cmd
0620
Set acknowledgement SMS
cmd
0621
Cancel acknowledgement SMS
cmd
0630
Set Alarm Message Text
cmd,id,s
id:1-128, s:0-31
0650
Set Remaining SMS Counter
cmd,v
v:0-4294967295
0660
Merge Concurrent Alarms
cmd
0661
Unmerge Concurrent Alarms
cmd
0783
Set GSM PIN
cmd,p
p:4
8.1.2 User configuration
Cmd
Description
Syntax
Comments
0500
Create User
cmd,id,n,p,c1,c2,c3,c4
Id:1-20, n:0-15, p:3-15, c1-c4: 0-1
(config users, config device, receive alarm
SMS, M2M flag)
0501 Delete
User
cmd,id
id:1-20
0502 Set
User
Configuration
cmd,id,c1,c2,c3
id:1-20, c1-c3: 0-1
(config users, config device, receive alarm)
1102
Set DI Alarm
Recipient
cmd,m,n,id
m:0-8, n:1-4, id:1-20
1202
Set AI Alarm
Recipient
cmd,m,n,id
m:0-4, n:1-2 (base) or 1-4 (ext), id:1-20
1109
Clear DI Alarm
Recipients
cmd,m,n m:0-8,
n:1-4
1209 Clear AI Alarm
Recipients
cmd,m,n m:0-4,
n:1-2
(base) or 1-4 (ext)