Transfer Switch

Page 7 of 16 Pages

5.0 Standard and Optional Features

Standard Features

The following standard features are provided with the LX-450 automatic transfer switch.

Indicating lights

NORMAL

(PL1, Green) When the transfer switch is in the normal position (normal source contacts

closed) auxiliary contact TSN-1NO closes to power the pilot light.

EMERGENCY

(PL2, Red) When the transfer switch is in the emergency position (emergency source

contacts closed) auxiliary contact TSE-1NO closes to power the pilot light.

Control Module

LED Indicators

EMERGENCY FREQUENCY MONITOR

LED (Green) This LED is on when the emergency source

frequency is within the operating range.

EMERGENCY VOLTAGE MONITOR

LED (Red) This LED is on when the emergency source voltage is

above the pick-up level.

ENGINE RUNNING UNLOADED

LED (Red) This LED is on when the engine generator is running

during the cool down interval.

NORMAL VOLTAGE MONITOR

LED (Green) This LED is on when the normal source voltage is above

the pick-up level.

RETRANSFER TO NORMAL SOURCE

LED (Red) This LED is on during the

RETRANSFER TO NORMAL

time delay after the normal source voltage rises above the pick-up level.

TRANSFER TO EMERGENCY SOURCE

LED (Red) This LED is on during the

TRANSFER TO

EMERGENCY

time delay after the emergency source voltage and frequency is above the pick-up level.

Time Delays

ENGINE RUNNING UNLOADED TIME DELAY

This time delay is provided to allow the engine

generator to run for a cool down period after retransfer to the normal source. At the end of this period,
the engine control relay contacts activate to shutdown the engine generator.

OVERRIDE MOMENTARY OUTAGES ON EMERGENCY SOURCE

This time delay overrides a

retransfer to the normal source when the emergency source voltage is low or drops out momentarily.

OVERRIDE MOMENTARY OUTAGES ON NORMAL SOURCE

This time delay overrides transfer

when the normal source voltage is low or drops out momentarily.

RETRANSFER TO NORMAL

This time delay allows the normal source to stabilize before retransfer.

TRANSFER TO EMERGENCY

This time delay allows the emergency source to stabilize before

retransfer.