Components, Assembly versions – Hubbell LX-440 User Manual
Page 13
Transfer Switch
Page 13 of 16 Pages
Components
1. Transfer Control Relay
Controls whether the automatic transfer switch is in the normal or the emergency position.
De-energized - automatic transfer switch in Normal position
Energized - automatic transfer switch in Emergency position
2. Timer circuit (not used on assembly –101 and -104)
This circuit determines how long the automatic transfer switch stays in the neutral position. Jumper
JMP1 selects one of four ranges.
Potentiometer P1 adjusts the time within that range. The four ranges are:
1–6 seconds
20–120 seconds
5–30 seconds
100–600 seconds
3.
Manual Disconnect
Switch
(not used on assembly -103)
Opening this switch disconnects power from the control transformers to the switching mechanism.
Then the transfer switch can only be switched manually using the handle.
Assembly versions
For LX-450
49271-101
No timer with MDS.
49271-102
Includes timer and MDS.
49271-104
No timer with MDS and monitor for AUTO/MANUAL switch.
49271-105
Includes timer, MDS, and monitor for AUTO/MANUAL switch.