Transfer Switch

Page 13 of 16 Pages

Components

1. Transfer Control Relay

Controls whether the automatic transfer switch is in the normal or the emergency position.

De-energized - automatic transfer switch in Normal position

Energized - automatic transfer switch in Emergency position

2. Timer circuit (not used on assembly –101 and -104)

This circuit determines how long the automatic transfer switch stays in the neutral position. Jumper
JMP1 selects one of four ranges.

Potentiometer P1 adjusts the time within that range. The four ranges are:

1–6 seconds

20–120 seconds

5–30 seconds

100–600 seconds

3.

Manual Disconnect

Switch

(not used on assembly -103)

Opening this switch disconnects power from the control transformers to the switching mechanism.
Then the transfer switch can only be switched manually using the handle.

Assembly versions

For LX-450

49271-101

No timer with MDS.

49271-102

Includes timer and MDS.

49271-104

No timer with MDS and monitor for AUTO/MANUAL switch.

49271-105

Includes timer, MDS, and monitor for AUTO/MANUAL switch.