SMV 3000 Transmitter User’s Manual

135

11.4

Diagnostic Messages,

Continued

Diagnostic Messages,
continued

Table 35

SFC Diagnostic Message Table

SMV Status

SCT Status Message SFC Display Message TDC Status Message

Possible Cause

What to Do

-

-

ALGPARM Kuser

>RANGE

-

Applicable PV4 algorithm
parameter is set to default value of
not-a-number (NaN).

Enter and download desired
value to transmitter database.

-

-

SAVE/RESTORE

H.W. MISMATCH

-

Hardware mismatch. Part of
Save/Restore function.

None – SFC tried to restore as
much of database as possible.

-

-

STATUS TAG ID.

NVM ON SEE MAN

-

SFC’s CPU is misconfigured.

Replace SFC.

-

-

SAVE/RESTORE

OPTION MISMATCH

-

On a database restore, one or more
options do not match.

None – SFC tried to restore as
much of database as possible.

-

-

STATUS TAG ID.

UNKNOWN

-

Selection is unknown.

Be sure SFC software is latest
version.

-

-

TAG NO.

LOW LOOP RES

-

Not enough resistance in series
with communication loop.

Check sensing resistor and
increase resistance to at least
250

.

-

-

TAG NO.

SFC FAULT

-

SFC is operating incorrectly.

Try communicating again. If error
still exists, replace SFC.

-

-

URV 1 . TAG ID.

>RANGE “H20_39F

-

SFC – Value calculation is greater
than display range.

SCT – The entered value is not
within the valid range.

SFC – Press [

CLR

] key and start

again. Be sure special units
conversion factor is not
greater than display range.

SCT – Enter a value within the

range.