4 diagnostic messages – Honeywell SMV 3000 User Manual
Page 138

126
SMV 3000 Transmitter User’s Manual
1/99
11.4
Diagnostic Messages,
Continued
Diagnostic Messages,
continued
Table 32
Non-Critical Status Diagnostic Message Table
SMV Status
SCT Status Message SFC Display Message TDC Status Message
Possible Cause
What to Do
9-3
Bad AP Compensation
PV4
STATUS TAG ID.#
BAD AP COMP PV4
BAD AP COMP PV4
Problem with absolute/gauge
pressure input PV2 or input
processing circuitry for PV2.
•
Verify that absolute/gauge
pressure input is correct for
selected flow equation.
•
If error persists, replace
transmitter.
9-4
Bad PT Compensation
PV4
STATUS TAG ID.#
BAD PT COMP PV4
BAD PT COMP PV4
Problem with process temperature
input PV3, input processing circuitry
for PV3, or PV4 algorithm
parameter data.
•
Verify that process
temperature input is correct.
•
Verify open/defective
temperature sensor.
•
Correct process temperature
measurement.
•
Check for temperature limits
exceeded in viscosity or
density configuration.
•
Check design temperature
value for PV4 standard gas
algorithm.
2-6
Corrects Reset PV1
STATUS TAG ID.#
CORRECTS RST PV1
CORRECTS RST PV1
All calibration “CORRECTS” were
deleted and data was reset for PV1
range.
Recalibrate PV1 (DP) range.
4-6
Corrects Reset PV2
STATUS TAG ID.#
CORRECTS RST PV2
CORRECTS RST PV2
All calibration “CORRECTS” were
deleted and data was reset.
Recalibrate PV2 (SP) range.
8-6
Corrects Active on PV3
STATUS TAG ID.#
CORR. ACTIVE PV3
CORR. ACTIVE PV3
Process temperature PV3 has been
calibrated and is now different than
factory default (uncalibrated).
Nothing – or do a reset corrects
Continued on next page