4 diagnostic messages – Honeywell SMV 3000 User Manual
Page 143

1/99
SMV 3000 Transmitter User’s Manual
131
11.4
Diagnostic Messages,
Continued
Diagnostic Messages,
continued
Table 32
Non-Critical Status Diagnostic Message Table, Continued
SMV Status
SCT Status Message SFC Display Message TDC Status Message
Possible Cause
What to Do
9-7
Reynolds Number is Out
of Range
-
STATUS 9-7
The high or low Reynolds number
limit was exceeded.
• Verify high or low Reynolds
number limit.
• Calculate Reynolds number
for flow conditions causing the
message.
8-7
Sensor Mismatch PV3
SAVE/RESTORE
TYPE MISMATCH
SNSR MISMTCH PV3
Number of wires selected does not
match number of sensor wires
physically connected to the
transmitter.
Check sensor wiring and type.