Rated Input Current

9.3 A (at 100 VAC)
9.7 A (at 110 VAC)
7.8 A (at 200 VAC)
7.2 A (at 208 VAC)
6.8 A (at 220 VAC)
6.2 A (at 240 VAC)

Rated Input Frequency

47 to 63 Hz

BTU Rating

BTU Rating

BTU Rating

BTU Rating

Maximum per power
supply

2728 BTU/hr (at 100 VAC)
3069 BTU/hr (at 120VAC)
4092 BTU/hr (at 200 to 240 VAC)

Power Specifications

Power Specifications

Power Specifications

Power Specifications

To review typical system power ratings use the Power Calculator which is
available via the online tool located at URL: :

www.hp.com/go/bladesystem/powercalculator

Power Supply Output

Power Supply Output

Power Supply Output

Power Supply Output
(per power supply)

Rated Steady-State Power 800 W (at 100 VAC),

900 W (at 120 VAC)
1200 W (at 200 to 240 VAC)

Maximum Peak Power

880 W (at 100 VAC),
990 W (at 120 VAC)
1350 W (at 200 to 240 VAC)

System Inlet Temperature

System Inlet Temperature

System Inlet Temperature

System Inlet Temperature Operating

10° to 35°C (50° to 95°F) at sea level with an
altitude derating of 1.0°C per every 305 m
(1.8°F per every 1000 ft) above sea level to a
maximum of 3050 m (10,000 ft), no direct
sustained sunlight. Maximum rate of change is
10°C/hr (18°F/hr). The upper limit may be
limited by the type and number of options
installed. System performance may be reduced if
operating with a fan fault or above 30°C (86°F).

Non-operating

-30° to 60°C (-22° to 140°F). Maximum rate of
change is 20°C/hr (36°F/hr).

Relative Humidity

Relative Humidity

Relative Humidity

Relative Humidity
(non-condensing)

Operating

10 to 90% relative humidity (Rh), 28°C (82.4°F)
maximum wet bulb temperature, non-
condensing.

Non-operating

5 to 95% relative humidity (Rh), 38.7°C
(101.7°F) maximum wet bulb temperature, non-
condensing.

Altitude

Altitude

Altitude

Altitude

Operating

3050 m (10,000 ft). This value may be limited by
the type and number of options installed.
Maximum allowable altitude change rate is 457
m/min (1500 ft/min).

Non-operating

9144 m (30,000 ft). Maximum allowable
altitude change rate is 457 m/min (1500 ft/min).

Acoustic Noise

Acoustic Noise

Acoustic Noise

Acoustic Noise

Listed are the declared A-Weighted sound power levels (LWAd) and declared
average bystander position A-Weighted sound pressure levels (LpAm) when
the product is operating in a 23°C ambient environment. Noise emissions
were measured in accordance with ISO 7779 (ECMA 74) and declared in
accordance with ISO 9296 (ECMA 109).
Idle

depends on server configuration & mix of server
blades

QuickSpecs

HP BladeSystem c3000 Enclosure

HP BladeSystem c3000 Enclosure

HP BladeSystem c3000 Enclosure

HP BladeSystem c3000 Enclosure

Technical Specifications

DA - 12790 Worldwide — Version 12 — July 14, 2008