Mixed Configuration – Full Height and Half Height Population

Mixed Configuration – Full Height and Half Height Population

Mixed Configuration – Full Height and Half Height Population

Mixed Configuration – Full Height and Half Height Population
The c3000 enclosure is divided into 2 zones or quadrants by the horizontal (vertical on Tower model) support metalwork. Zone 1
includes bays 1, 2, 4, & 5; and Zone 2 contains bays 3, 4, 7, & 8. Within each zone a removable divider is used to support half
height devices. To install a full-height blade in any zone this divider must be removed. An optional mini-divider support bracket is
included with every c3000 enclosure. As a consequence of using the mini-divider in the Zone 2, this zone can only contain one full
height blade and 2 half-height blades. Zone 1 can contain either 4 half-height blades, or by removing the divider, it can contain 2
full-height blades.

NOTE:

NOTE:

NOTE:

NOTE: Please read the RTF card (included with each c3000 enclosure) and the "HP BladeSystem c3000 Setup and Installation
Guide" for more information on using bay dividers and the mini-divider for mixed configurations.

NOTE:

NOTE:

NOTE:

NOTE: Storage or tape blades can be installed in the same zone as both full-height and half-height blades, a bracket ships with
each SB40c that allows a half-height blade to be mounted to the left side of a storage or tape blade.

NOTE:

NOTE:

NOTE:

NOTE: In this case, the SB40c or tape blade cannot be removed without first removing the half height blade and mounting bracket.

NOTE:

NOTE:

NOTE:

NOTE: For Mixed configurations of full height and half height population rules; please see the c3000 Enclosure installation and
users guide at:

http://h71028.www7.hp.com/enterprise/cache/316682-0-0-0-121.html

Enclosure Unit –

Enclosure Unit –

Enclosure Unit –

Enclosure Unit –
Rack Model

Rack Model

Rack Model

Rack Model

Dimensions

Dimensions

Dimensions

Dimensions (H x W x D)
(with bezel)

10.4 x 19.1 x 32.977 in (265 x 485 x 835 mm)

Weight

Weight

Weight

Weight
(approximate)

Maximum
(one enclosure with 8
blades and 4 interconnects
installed)

300 lb (136 kg)

Minimum
(one enclosure without
blades and interconnects)

130 lb (59 kg)

Input Requirements

Input Requirements

Input Requirements

Input Requirements
(per AC power supply)

Rated Line Voltage

90 –

– 132 VAC

180 –

– 264 VAC

Rated Input Current

9.3 A (at 100 VAC)
9.7 A (at 120VAC)
7.8 A (at 200 VAC)
7.2 A (at 208 VAC)
6.8 A (at 220 VAC)
6.2 A (at 240 VAC)

Rated Input Frequency

47 to 63 Hz

BTU Rating

BTU Rating

BTU Rating

BTU Rating

Maximum per power
supply

2728 BTU/hr (at 100 VAC)
3069 BTU/hr (at 120VAC)
4092 BTU/hr (at 200 to 240 VAC)

Power Specifications

Power Specifications

Power Specifications

Power Specifications

To review typical system power ratings use the Power Calculator which is
available via the online tool located at URL:

www.hp.com/go/bladesystem/powercalculator

Power Supply Output

Power Supply Output

Power Supply Output

Power Supply Output
(per power supply)

Rated Steady-State Power 800 W (at 100 VAC)

900 W (at 120 VAC)
1200 W (at 200 to 240 VAC)

Maximum Peak Power

880 W (at 100 VAC)
990 W (at 120 VAC)
1350 W (at 200 to 240 VAC)