beautypg.com

Quickspecs, Hp 9000 superdome servers – HP PA 8800 User Manual

Page 36

background image

HP-UX Attributes

HP-UX Attributes

HP-UX Attributes

HP-UX Attributes

Maximum CPUs per HP-UX 11i
partition

16

32

64

Maximum CPUs per HP-UX 11i
partition

16

32

128

Maximum memory per HP-UX
11i partition

128 GB

256 GB

512 GB

Maximum memory per HP-UX
11i partition

128 GB

256 GB

1 TB

HP-UX revisions supported

HP-UX 11i, HP-UX 11i v2

HP-UX 11i, HP-UX 11i v2

HP-UX 11i, HP-UX 11i

v2

Maximum I/O Cards See supported I/O table for specific products

Maximum I/O Cards See supported I/O table for specific products

Maximum I/O Cards See supported I/O table for specific products

Maximum I/O Cards See supported I/O table for specific products

Mass Storage

16 - 48

32 - 96

64 - 192

LAN

8 - 24

16 - 48

32 - 96

WAN

8 - 25

16 -25

25 -32

Multi-Function (Mass Storage /
LAN)

8 - 16

16 -32

32 -64

Additional Interface Cards

8

8 -16

8 -32

Electrical Characteristics

Electrical Characteristics

Electrical Characteristics

Electrical Characteristics

AC input power-Option 7: 3-
phase 5-wire input

200-240 VAC phase-to-neutral, 5-wire, 50/60 Hz

AC input power-Option 6: 3-
phase 4-wire input

200-240 VAC phase-to-phase, 4-wire, 50/60 Hz

Maximum Current requirements
at 220V 240V:

Option 7:
3-phase 5-wire input

24 A/Phase

Option 6:
3-phase 4-wire input

44 A/Phase

Required Power Receptacle-
Options 6 and 7

None. Cord, plug and included. Receptacle should be ordered separately. Electrician must

hard wire receptacle to site power.

Site Preparation

Site Preparation

Site Preparation

Site Preparation

Site planning and installation
included

Yes

Yes

Yes

Depth (mm / inches)

1,220 / 48.1

1,220 / 48.1

1,220 / 48.1

Width (mm / inches)

762 / 30

762 / 30

1,524 / 60

Height (mm / inches)

1,960 / 77.2

1,960 / 77.2

1,960 / 77.2

Weight (Kg / lbs)

500 / 1,123

598 / 1,343

1,196 / 2,685

Environmental Characteristics

Environmental Characteristics

Environmental Characteristics

Environmental Characteristics

Acoustics

65 dB

Operating temperature

68° to 86° F (20° to 30° C)

Non-operating temperature

-40° to 158° F (-40° to 70° C)

Maximum rate of temperature
change

68° F/hr (20° C/hr)

Operating relative humidity

15% to 80% @ 86° F (30° C)

Operating altitude

0 to 10,000 ft (0 to 3.1 km)

Non-operating altitude

0 to 15,000 ft (0 to 4.6 km)

QuickSpecs

HP 9000 Superdome Servers

HP 9000 Superdome Servers

HP 9000 Superdome Servers

HP 9000 Superdome Servers

(PA-8600, PA-8700 and PA-8800)

(PA-8600, PA-8700 and PA-8800)

(PA-8600, PA-8700 and PA-8800)

(PA-8600, PA-8700 and PA-8800)

Technical Specifications

DA - 11721 North America — Version 13 — April 1, 2005

Page 36

This manual is related to the following products: