HP T2200 User Manual
Page 11

Component identification 11
•
The REPO feature shuts down UPS units operating under either utility or battery power.
Option 2: User supplied normally closed switch
NOTE:
If the UPS was operating on battery power when the remote switch was closed, no
power is available to the load devices until utility power is restored and the UPS has been
manually powered up.
To restore power to the load devices after the REPO feature is activated, press the Power On/Standby
button after the AC source is reconnected to the UPS.
IMPORTANT:
Pressing and holding the Power On/Standby button without utility present
normally initiates a battery start and the UPS assumes the load. However, if the Power
On/Standby button is pressed and a REPO is detected, battery start is inhibited and the UPS is
not able to assume the load.
To power down the entire network in the event of an emergency, the REPO ports of multiple UPS units can
be connected to a single switch.