Repo port – HP T2200 User Manual
Page 10
Component identification 10
Item Description
3
Load segment 3 (one IEC-320-C13 output receptacle for
surge and battery backup protection)
4
Load segment 4 (five unswitchable IEC-320-C13 output
receptacles for surge and battery backup protection)
5
Input circuit breaker
6
Input power cord with IEC-320-C20 plug
7
Serial communications port
8
USB communications port
9 REPO
port
10
Voltage configuration and charge rate DIP switches
11
Power sensitivity adjustment dial
12
Ground bonding screw
13 ERM
connector
For information about controlling load segments remotely, see "Power management software (on page
REPO port
The UPS includes an RJ-11 type EPO port. The EPO function can be used to power down the UPS output
receptacles in an emergency. This feature is enabled by utilizing a normally open (N.O.) switch (option 1)
or a normally closed (N.C.) switch (option 2). The EPO port is referred to as a REPO port when used in
conjunction with a remote main disconnect device that shuts down utility power in an emergency.
Option 1: User supplied normally open switch
When the switch is enabled:
•
The REPO feature immediately powers down protected devices and does not utilize the orderly
shutdown procedure initiated by power management software.