beautypg.com

Harman Stove Company HARMAN Super Magnum Coal Stoker Stove User Manual

Page 21

background image

21

Do Not Burn Wet Coal!

Super-Magnum Coal Stoker Stove

3-90-02702R6_03/13

a. Feed Rate Adjustment

The Circuit board runs on a one minute timer cycle. Each

minute, the board is thinking ahead to what it needs to do

for the next minute to maintain or achieve the demanded

temperature. What you are setting on the feed adjuster dial

is the maximum amount of feed time, per minute, that you'll

allow. The circuit board will make its own determination of

how long to run the feeder, UP TO the maximum as set

on the dial. For instance, a number 4 setting on the feed

adjuster will allow a maximum of 40 seconds per minute of

feed. If the room temperature is satisfied, with only feeding

20 seconds, then that is all the circuit board will run the

feeder. In most tested scenarios, the number 4 setting is

adequate, however, fuel quality may dictate a higher or

lower setting. If you see un-burned or burning coal being

pushed off of the grate during a high demand period, the

feed rate is set too high. Ideally, you'll want to see about

an inch of ashes in front of the burning coal during a peak

demand period. Setting the feed rate too low may not allow

the demand temperature to be met. Keeping the setting at

#4 or above will work with most batches of coal. Allow a

minimum of one hour between adjustments.
Note: Since the circuit board is feeding as needed,

only adjust the feed rate while maximum demand is

occurring. (Stove Temp Mode, with a temp dial setting

of #7 will create maximum demand.)

b. Mode Selection

Room-Temp mode is the ideal mode of operation if you

wish to maintain a comfortable temperature in the room.

As the outdoor temperature fluctuates, the Super Magnum

will adjust the feed rate to maintain the desired temperature

setting in the room. For best results, be sure the room sensor

is located outside of any drafty areas and not positioned on

the floor or near an exterior wall.
Stove-Temp mode is more of a manual method of operation.

The stove will run at a constant heat output, regardless of

outside air temperature. Note that on the coldest days, your

indoor heated space will be cooler than on the warmer

days. The only real benefit to this mode of operation is that

you'll be able to know exactly how long a hopper full of coal

will last, because the consumption is going to stay relatively

the same.

c. Temperature Dial

The temperature dial is a dual purpose dial. In Room-Temp

mode, you select the room temperature you want the stove

to maintain at the room sensor probe. This is marked in

fahrenheit scale from 50 to 90 degrees. In Stove-Temp

mode, you select a temperature setting based on the #1 - 7

with 1 being a minimum burn and 7 being a maximum burn

rate.

d. Blower Speed Adjustment

The mode selector is also marked with a L to H scale, in each

mode. This is a variable speed control for the distribution

blower.

L is the low setting, and H is the high setting. It

is important to note that the blower will not come on until

the ESP reaches a high enough temperature to ensure that

cold air is not being blown out into the room. Also, the speed

of the blower, when set on lower speeds, will automatically

increase as the temperature of the stove increases.
Keep Hopper Lid, Ash Pan, and Fire viewing doors

closed while in operation. Maintain all door seals and

gaskets in good condition. Replace gaskets when

necessary using parts obtianed through your Harman

dealer.
Burning with one or more of the unit doors open will

lead to overfiring which could damage the appliance,

chimney, or connector, or could cause a house fire.