beautypg.com

Gas information, Warning – Heat & Glo Fireplace Heat & Glo 350TRSILP-AUF User Manual

Page 52

background image

Heat & Glo • 350TRSI-AUF, 350TRSILP-AUF • 2089-980 Rev. R • 2/13

52

11

Gas Information

A. Gas Pressure Requirements

WARNING! Risk of Explosion! An in-line regulator

MUST be installed if the gas pressure exceeds 3.7 kPa.

Failure to install a regulator could damage valve.
Pressure requirements for 350TRSI-AUF and 350TRSILP-

AUF fireplaces are shown in the table below.
Two taps are provided on the right hand side of the gas

control for a test gauge connection to measure the inlet

and outlet pressures.
The fireplace and its individual shut-off valve must be dis-

connected from the gas supply piping system during any

pressure testing of the system at test pressures in excess

of 6 kPa.
If the fireplace must be isolated from the gas supply pip-

ing system by closing an individual shut-off valve, it must

be of the handle-less type.

Incoming gas line should be piped into the valve compart-

ment and connected to the ISO 7-Rp 1/2 (BSP Rp 1/2)

threaded gas inlet connection on the manual shutoff valve.
Leak test all gas line points and the gas control valve prior

to and after starting the gas appliance.

B. Gas Connection

Note: Have the gas supply line installed in accordance with

local building codes by a qualified installer approved and/or

licensed as required by the locality.

Note: Before the first firing of the appliance, the gas supply

line should be purged of any trapped air.

Note: Consult local building regulations to properly size the

gas supply line leading to the (Rp 1/2 in.) hook-up at the unit.

WARNING

CHECK FOR GAS LEAKS
Explosion Risk
Fire Risk
Asphyxiation Risk
• Check all fittings and connections.
• Do not use open flame.
• After the gas line installation is complete, all

connections must be tightened and checked

for leaks with a commercially-available, non-

corrosive leak check solution. Be sure to rinse

off all leak check solution following testing.

Fittings and connections may have loosened

during shipping and handling.

WARNING

Fire Risk

Explosion Risk

High pressure will damage valve.

• Disconnect gas supply piping BEFORE

pressure testing gas line at test pressures

above 6 kPa.

• Close the manual shutoff valve BEFORE

pressure testing gas line at test pressures

equal to or less than 6 kPa.

Natural Gas

Propane

Inlet Gas Pressure

1.13 - 3.40 kPa

2.75 - 3.40 kPa

Outlet (Manifold) Gas Pressure

.80- .95 kPa

2.36 - 2.61 kPa

Maximum Gas Consumption

21 MJ/h

19.8 MJ/h

Burner Injector

DMS 44 (2.18 mm)

DMS 55 (1.32 mm)

Pilot Injector

.0181

.0121

An in-line regulator MUST be installed if the gas pressure exceeds

3.40 kPa. Failure to install a regulator could damage

valve.

Leak test all gas line points and the gas control valve prior

to and after starting the gas appliance.

IMPORTANT NOTICE:

(Items 1, 2 and 3 applies to

ALL Heat & Glo gas appliances)
1. 1/2 in. GAS LINE: Run through cavity 70 mm

above finished hearth level,

NOT RIGID, NOT

CLIPPED, with minimum 500 mm into cavity and

120 mm back from plaster face.

2. PVC (COMPOSITE) GASLINE must terminate

minimum 500 mm short of gas heater. Copper pipe

MUST be the final connection to the gas heater.

3. ISOLATING SWITCH: Location within 1 metre

of fireplace, subject to mantelpiece etc. Check to

ensure it remains clear of any mantelpiece instal-

lation.

This manual is related to the following products: