Top vent - horizontal termination - (continued), Two elbows – Heat & Glo Fireplace Heat & Glo 350TRSILP-AUF User Manual

Page 28

background image

Heat & Glo • 350TRSI-AUF, 350TRSILP-AUF • 2089-980 Rev. R • 2/13

28

Top Vent - Horizontal Termination - (continued)

Figure 7.5

Two Elbows

V

1

Minimum

H

1

+ H

2

Maximum

Elbow only

Not allowed

6 in.

152 mm

1 ft.

305 mm

1 ft.

305 mm

2 ft.

610 mm

2 ft.

610 mm

4 ft.

1.22 m

3 ft.

914 mm

6 ft.

1.83 m

4 ft.

1.22 m

8 ft.

2.44 m

5 ft.

1.52 m

10 ft.

3.05 m

30 ft.

9.14 m

10 ft.

3.05 m

V

1

+ H

1

+ H

2

= 30 ft. (9.14 m) Maximum

H

1

+ H

2

= 10 ft. (3.05 m) Maximum

INSTALLED

HORIZONTALLY

H

1

H

2

V

1

USE SLP SERIES COMPONENTS ONLY

Note: A 6 in. (152 mm) section of straight flue must

be attached to the heater before a 90° elbow.