beautypg.com

Two elbows, Top vent - vertical termination - (continued) – Heat & Glo Fireplace Heat & Glo 350TRSILP-AUF User Manual

Page 32

background image

Heat & Glo • 350TRSI-AUF, 350TRSILP-AUF • 2089-980 Rev. R • 2/13

32

Figure 7.10

Two Elbows

V

1

H

1

Maximum

V

2

V

1

+ V

2

Min.

Elbow only

Not allowed

*

*

*

6 in.

152 mm 2 ft. 610 mm

*

*

*

1 ft.

305 mm

4 ft.

1.22 m

*

*

*

2 ft.

610 mm

6 ft.

1.83 m

*

*

*

3 ft.

914 mm

8 ft.

2.44 m

*

*

*

4 ft.

1.22 m

12 ft. 3.66 m

*

*

*

5 ft.

1.52 m

16 ft. 4.88 m

*

*

*

V

1

+ V

2

+ H

1

= 36 ft. (10.97 m) Maximum

*No specific restrictions on this value EXCEPT

V

1

+ V

2

cannot exceed 32 ft. (9.75 m)

H

1

V

1

V

2

Top Vent - Vertical Termination - (continued)

USE SLP SERIES COMPONENTS ONLY

Note: A 6 in. (152 mm) section of straight flue

must be attached to the heater before a 90° elbow.

This manual is related to the following products: