beautypg.com

Vent information and diagrams, A. approved pipe, C. use of elbows – Heat & Glo Fireplace Heat & Glo 350TRSILP-AUF User Manual

Page 26: B. vent table key, D. measuring standards, E. vent diagrams

background image

Heat & Glo • 350TRSI-AUF, 350TRSILP-AUF • 2089-980 Rev. R • 2/13

26

A. Approved Pipe

This appliance is approved for use with Hearth & Home

Technologies DVP and SLP venting systems. Refer to

Section 16.B for vent component information.
DO NOT mix pipe, fittings or joining methods from differ-

ent manufacturers.
The pipe is tested to be run inside an enclosed wall.

There is no requirement for inspection openings at each

joint within the wall.
WARNING! Risk of Fire or Asphyxiation. This appli-

ance requires a separate vent.

DO NOT vent to a pipe

serving a separate solid fuel burning appliance.

7

Vent Information and Diagrams

C. Use of Elbows

Diagonal runs have both vertical and horizontal vent as-

pects when calculating the effects. Use the rise for the

vertical aspect and the run for the horizontal aspect (see

Figure 7.1).
Two 45º elbows may be used in place of one 90º elbow.

On 45º runs, one foot of diagonal is equal to 8-1/2 in. (216

mm) horizontal run and 8-1/2 in. (216 mm) vertical run. A

length of straight pipe is allowed between two 45º elbows

(see Figure 7.1).

Figure 7.1

B. Vent Table Key

The abbreviations listed in this vent table key are used in

the vent diagrams.

D. Measuring Standards

Vertical and horizontal measurements listed in the vent

diagrams were made using the following standards.
• Pipe measurements are shown using the effective length

of pipe (see Figure 7.2 and 7.3).

• Measurements are made from the appliance outer wrap,

not from the standoffs.

• Horizontal terminations are measured to the outside

mounting surface (flange of termination cap).

• Vertical terminations are measured to bottom of

termination cap.

• Horizontal pipe installed level with no rise.

Symbol

Description

V

1

First section (closest to appliance) of vertical length

V

2

Second section of vertical length

H

1

First section (closest to appliance) of horizontal length

H

2

Subsequent sections of horizontal length

Horizontal

Vertical

8-1/2 in.

(216 mm)

8-1/2 in. (216 mm)

12 in.

(305 mm)

E. Vent Diagrams

General Rules:
• When penetrating a combustible wall, a wall shield

firestop must be installed.

• When penetrating a combustible ceiling, a ceiling firestop

must be installed.

• Horizontal runs of vent do not require vertical rise;

horizontal runs may be level.

Figure 7.2 DVP Pipe Effective Length

Figure 7.3 SLP Pipe Effective Length

Effective Height/Length

Pipe

inches

mm

DVP4

4

102

DVP6

6

152

DVP12

12

305

DVP24

24

610

DVP36

36

914

DVP48

48

1219

DVP6A

3 - 6

76 - 152

DVP12A

3 - 12

76 - 305

Effective

Height/

Length

Effective

Height/

Length

Effective Height/Length

Pipe

inches

mm

SLP4

4

102

SLP6

6

152

SLP12

12

305

SLP24

24

610

SLP36

36

914

SLP48

48

1219

SLP6A

2 - 6

51 - 152

SLP12A

2 - 12

51 - 305

This manual is related to the following products: