Refrigeration Load Estimate Form
(for rooms above 32ºF) Bulletin Above32-05

Basis for Estimate
Room Dimensions: Width

ft. x Length

ft. x Height

ft.

Volume: (L)

x (W)

x (H) = cu. ft.

Ambient Temp ºF. (Corrected for sun load) — Room Temp ºF. = ºF. T.D.

Product Load

(a) lbs./day of to be reduced from entering

temp. of ºF. to ºF. Temp. Drop ºF.

(b) lbs./day of to be reduced from entering

temp. of ºF. to ºF. Temp. Drop ºF.

Miscellaneous

Motors (including all blower motors) HP Ground Temp. (Table 21)

Lights (assume 1 watt/sq.ft.) Watts

No. of people

2. Air Change Load

Volume: cu. ft. x Factor (Table 4) x Factor (Table 6)

=

3. Additional Loads

Electrical Motors: HP x 75000 BTU/HP/24 hr.

=

Electrical Lights: Watts x 82

=

People Load: People x BTU/24 hrs. (Table 12)

=

Glass Door Load: Doors x 19200 BTU/Door/24 hr.

=

4. Product Load: Sensible (Product Load Figured @ 24 hr. Pulldown*)

(a) lbs./day x Spec. Heat (Table 7) x ºF. Temp Drop

=

(b) lbs./day x Spec. Heat (Table 7) x ºF. Temp Drop

=

*For product pulldown time other than 24 hrs. figure 24 hr. load x (24/Pulldown Time)

5. Product Load: Respiration*

(a) lbs. stored x BTU/lbs./24 hrs. (Table 8)

=

(b) lbs. stored x BTU/lbs./24 hrs. (Table 8)

=

*For consideration of previously loaded product, a multiplier of (5) is normally applied to the daily

product load (Line #4)

Divide by No. of Operating Hrs. (16) to obtain BTUH Cooling Requirement

Equipment Selection

Condensing Unit

Unit Cooler

System Capacity

Qty. Model No.

Qty. Model No.

BTU/hr.

Total Refrigeration Load (1+2+3+4+5) BTU/24 hrs.
Add 10% Safety Factor
Total with Safety/Factor BTU/24 hrs.

1. Transmission Loads

Ceiling: (L)

x (W)

x Heat Load

(Table 1)

=

North Wall: (L)

x (W)

x Heat Load

(Table 1)

=

South Wall: (L)

x (W)

x Heat Load

(Table 1)

=

East Wall: (L)

x (W)

x Heat Load

(Table 1)

=

West Wall: (L)

x (W)

x Heat Load

(Table 1)

=

Floor: (L)

x (W)

x Heat Load

(Table 1)

=

Insulation

Inches

Ceiling

Walls

Floor

Type

2175 West Park Place Blvd. • Stone Mountain, GA 30087 • 770.465.5600 • Fax: 770.465.5990 • www.heatcraftrpd.com

Estimate for:

Estimate by:

Date:

Note: Tables can be found in
Engineering Manual, H-ENG-2

(H)

(H)

Example: 35ºF Convenience Store Cooler With Glass Doors

8 28 8

28 8 8 1792

85 35 50

4 Styrene

4 Styrene

6 Concrete

2000 Beer

85 35 50

200 Milk

40 35 5

0.2 60

224

0

28 8 72 16128

28 8 72 16128

28 8 72 16128

8 8 72 4608

8 8 72 4608

28 8 125 28000

1792 13 1.86 43331

0.2 15000

224 18368

0 —

10 192000

2000

0.92 50 92000

200

0.93 5 930

— — —

— — —

447229

44723

491952

30747