Table 30.

Conversion Factors (constant)

Water

500 = 8.33 lbs./gal. x 60 min,

– (Converts GPM to lbs./hr.)

Air

4.5 = 60 min

13.35 Cu. Ft./lb.

– (Converts CFM to lbs./hr.)

1.08 = 4.5 x 0.241 BTU/lb./ºF.

– (lbs./hr. x Sp. Ht. of Air)

0.68 = 4.5 x 1054.3 BTU/lb.

7000 gr/lb.

– (4.5 combined with heat

of vaporization of water

at 70ºF. and grains per

pound of water)

Water Heating, Cooling & Heat Reclaim Coils, Water Chillers,

Condensers, etc.

Q = 500 x GPM x T

= BTU/hr.

T = Q

500 x GPM

For brines, Q = 500 x GPM x T x (Sp. Ht. x Sp. Gr. of Brine)

Air Coils

Q Sensible = 1.08 x CFM x T

= BTU/hr.

Q Latent = 0.68 x CFM x SH

= BTU/hr.

Q Total = 4.5 x CFM x H = BTU/hr.

lb./hr. Condensate

= 4.5 x CFM x SH Grains

7000 grains/lb

SHR Sensible Heat Ratio = Q Sensible

Q Total

Heat Transmission

Q Total = U x A Surface x T

= BTU/hr.

Product

Sensible Heat in BTU/hr. = lbs/hr. x Sp. Ht. x T

Latent Heat in BTU/hr.

= lbs/hr. x Lt. Ht. in Btu/lb.

Heat of Resp. in BTU/hr .

= lbs x Heat or Respiration

in BTU/lb./hr.

All conversion factors used in standard calculations must be

corrected for other than standard properties

Properties of Water at 39.2 ºF.

Density of Water

= 62.4 lbs./Cu. Ft.

Specific Heat of Water

= 1 BTU/lb./ºF.

Latent Heat of

= 970 BTU/lb. at 212ºF. & Atm.

Vaporization

= 1054.3 BTU/lb. at 70ºF.

Specific Heat of Ice

= 0.5 BTU/lb./ºF.

Latent Heat of Fusion

= 144 BTU/lb.

1 Gallon of Water

= 8.33 lbs.

1 Pound of Water

= 7000 Grains

Nomenclature

Q = Heat Flow in BTU/hr.

T = Temperature in ºF. ( T = temp. diff.)

A = Area in Sq. Ft.

U = Coef. of Heat Transfer in BTU/hr./Sq.Ft./ºF.

H = Total heat of air at wet bulb temp. BTU/lb.

H = Enthalpy difference between entering & leaving air

SH = Specific humidity in grains of moisture/lb. of dry air

( SH = Specific humidity difference for entering

and leaving air)

CFM = Cu. Ft./min.

GPM = Gal/min.

W

I

R

E

I

2

X R

E X I

I X R

E

2

W

E

R

E

R

W

E

W

I

W

I

2

E

I

W

R

W X R

Table 31.

Single Phase Loads

Ohm’s Law for direct current

W = Watts

I = Current (Amperes)

E = Electromotive Force (Volts)

R = Resistance (Ohms)

To obtain any values in the center circle, for Direct or Alternating

Current, perform the operation indicated in one segment of the

adjacent outer circle.

3 Phase Delta Loads

3 0 Balanced Loads = P

1

+ P

2

+ P

3

Total Line Current = Total Power (Balanced Load)

If the phase are unbalanced, each of the phase will differ from

the others:

FORMULAE:

I

L1 =

I

2 +

I

2 + (

I

1 X

I

2 )

3 1

I

L2 =

I

2 +

I

2 + (

I

2 X

I

3 )

2 3

I

L3 =

I

2 +

I

2 + (

I

1 X

I

3 )

3 1