6. Hourly Heat Load

The hourly heat load serves as the guide in selecting

equipment. It is found by dividing the final BTU/24 hour load

by the desired condensing unit run time.

35ºF. rooms with no timer 16 hr.

35ºF. rooms with timer

18 hr.

Blast coolers/Freezers with

positive defrost

18 hr.

Storage Freezers

18-20 hr.

25ºF. - 34ºF. coolers with hot gas

or electric defrost

20-22 hr.

50ºF. rooms and higher with coil

temperature above 32ºF. 20-22 hr.

7. Load Calculation Forms

To simplify the calculation and tabulation of refrigeration

loads, there are two forms available:

Bulletin Above32-05 is used for all rooms above 32ºF. (0ºC.)

Bulletin Below32-05 is used for all rooms below 32ºF. (0ºC.)

All data and tables necessary to fill in the Load Calculation

Forms can be found in this manual.

A Word of Caution: The refrigeration load calculation

methods presented in this manual are intended for use

in selecting refrigeration equipment for rooms used for

holding and sometimes pulling product temperature down.

For process or unusual applications such as blast freezing or

food processing situations, please contact our Application

Engineering Department.