beautypg.com

Heatcraft Refrigeration Products H-ENGM0408 User Manual

Page 5

background image

5

[ (4.88) ( door height) (area/2) (minutes open) ( temp. diff. ºF.)
(enthalpy incoming air – enthaply warehouse air) ] [ (1–X)]
Specific Volume of Incoming Air

Where X = % of heat transmission blocked by thermal barrier.

For freezers it becomes necessary to provide heat in the base slab

to avoid freezing of the ground water and heaving of the floor.

Minimum slab temperature should be at least 40ºF. Normally, 55ºF.

should be used for freezer applications.

2. Air Change Load

(a) Average Air Change- when the door to a refrigerated room is

opened, warm outside air will enter the room. This air must be

cooled to the refrigerated room temperature, resulting in an

appreciable source of heat gain. This load is sometimes called

the infiltration load. The probable number of air changes per

day and the heat that must be removed from each cubic foot

of the infiltrated air, are given in tables based on experience

(see Table 4, 5 & 6, page 14). For heavy usage, the infiltration

may be doubled or more.

(b) Infiltration Through a Fixed Opening- As an alternate to the

average air change method using the Psychrometric Chart

(page 37), the following formulas may be used to calculate

the infiltration resulting from natural ventilation (no wind)

through external door openings.

The air change load can be substantial and every means

should be taken to reduce the amount of infiltration entering

the box. Some effective means of minimizing this load are:

• Automatic closing refrigerator doors

• Vestibules or refrigerated anterooms

• Plastic strip curtains

• Air Curtains

• Inflated bumpers on outside loading doors.

3. Miscellaneous Loads

Although most of the heat load in a refrigerated room

or freezer is caused by wall heat leakage, air changes and

product cooling or freezing, there are three other heat

sources that should not be overlooked prior to the selection

of the refrigeration equipment. Since the equipment has to

maintain temperature under design conditions, these loads are

generally averaged to a 24 hour period to provide for capacity

during these times.

(a) Lights- typically storage requirements are 1 to 1-1/2 watt per

square foot. Cutting or processing rooms can be double the

wattage. Each watt is multiplied by 3.42 BTU/watt to obtain a

BTUH figure. This is then multiplied by 24 to obtain a

daily figure.

(b) Motors- smaller motors are usually less efficient and tend to

generate more heat per horsepower as compared to larger

motors. For this reason Table 11, on page 18, is broken down

in to H.P. groups. Also, motors inside the refrigerated area will

reject all of their heat losses as shown in Table 11. However,

motors that are located outside but do the work inside, like

a conveyor, will reject less heat into the refrigerated space. If

powered material handling equipment is used, such as forklift

trucks, this must be included under Motor Heat Loads.

Generally only battery operated lift trucks are used in

refrigerated rooms, which represent a heat gain of 8,000 to

15,000 BTU/hr. or more over the period of operation. If motor

or loading conditions are not known, then calculate one

motor horsepower for each 16,000 cubic foot box in a storage

cooler and one HP for each 12,500 C.F. in a storage freezer

which allows for fan motors and some forklift operations.

These figures can be higher in a heavily used area, i.e. loading

dock or distribution warehouse.

(c) Occupancy- People working in the refrigerated storage area

dissipate heat at a rate depending on the room temperature

(Table 12, page 18). Multiple occupancies for short periods

should be averaged over a 24 hour period. If occupancy load

is not known, allow one person per 24 hour for each 25,000

cubic foot space.

4. Product Load

Whenever a product having a higher temperature is placed

in a refrigerator or freezer room, the product will lose its

heat until it reaches the storage temperature. This heat load

consists of three separate components: (see Table 7, page 15-

16).

(a) Specific Heat- The amount of heat that must be removed

from one pound of product to reduce the temperature of this

pound by 1ºF., is called its specific heat. It has two values: one

applies when the product is above freezing; the second is

applicable after the product has reached its freezing point.

(b) Latent Heat- The amount of heat that must be removed from

one pound of product to freeze this pound is called the latent

heat of fusion.

Most products have a freezing point in the range of 26ºF. to

31ºF. If the exact temperature is unknown, it may be

assumed to be 28ºF.

There is a definite relationship between the latent heat of

fusion and the water content of the product and its specific

and latent heats.

Estimating specific and latent heats:

Sp. Ht. above freezing = 0.20 + (0.008 X % water)

Sp. Ht. below freezing = 0.20 + (0.008 X % water)

Latent Heat = 143.3 X % water

(c) Respiration- Fresh fruits and vegetables are alive. Even in

refrigerated storage they generate heat which is called the

heat of respiration. They continually undergo a change in

which energy is released in the form of heat, which varies with

the type and temperature of the product. Tabulated values are

usually in BTU/lb./24 hours (Table 8, page 17), and are applied

to the total weight of product being stored and not just the

daily turnover.

(d) Pull down Time- When a product load is to be calculated at

other than a 24 hour pull down, a correction factor must be

multiplied to the product load.

24 hours

Pull down Time

Note: While product pull down can be calculated, no

guarantee should be made regarding final product

temperature due to many uncontrollable factors (i.e., type of

packaging, position in the box, method of stacking, etc.)

5. Safety Factor

When all four of the main sources of heat are calculated,

a safety factor of 10% is normally added to the total

refrigeration load to allow for minor omissions and

inaccuracies (additional safety or reserve may be available

from the compressor running time and average loading).

This manual is related to the following products: