32

INSTALLER SETTING

ENGLISH

INSTALLER SETTING

33

ENGLISH

Function setting

Fahrenheit / Celsius

Value 2 : Setting value

Value 1 : Select mode

ڸ

ڹ

ں

Outdoor
Temperature

T1 +

Ɲ

T

T1

Time

h

Press button to select value 1 or value 2.

Value 1

Select mode

1

Use/Not use setting

2

T1 value setting

3

T value setting

Setting value

Description

0

Not use

1

Use

Value 1 : 01

Value 1 : 02

Value 1 : 03

Temperature unit

T1 setting range

Celsius

-23~16°C

Fahreneit

-10~60°F

[-9°F or higher]

[-10°F or lower]

Temperature unit

T setting range

Celsius

0~35°C

Fahreneit

0~70°F

Operation according to T1,

T setting and out-

door temperature.

Value 1 00 : Not used

- According to the outdoor unit operation

mode, operation mode selection is limited.

h

The following operation modes can be se-

lected according to the outdoor unit cycle.

- Cooling cycle: auto, fan, cool, dehumidifi-

cation

- Heating cycle: auto, fan, heat

Value 1 01 : Standby

- In case of the operation mode opposite to

the outdoor unit operation mode, it maintains

the current operation mode. At this time, it

maintains thermal off + fan off state.

Value 1 02 : Priority cooling

- Outdoor unit operation has priority in cooling

operation. It is the function to enable the

heating operation by heater in the product in

heating operation.

h

For heater interface operation, set ‘emer-

gency heater setting' and ‘auxiliary heater’.

- Emergency heater setting – installer code

18

- Auxiliary heater – installer code 25

Value 2 : Waiting
time for cooling
thermal off

Value 1 : Mode setting

Function code

h

Press button to select value 1 or value 2.

Value 2 Waiting time for cooling thermal off

0

45 minutes (default)

1

30 minutes

2

60 minutes

3

90 minutes

4

120 minutes

5

Not use

Outdoor temperature for heating
stages (Code 57)

It is a function that sets outdoor temperature

values for two stages heating. If user sets out-

door temperature T1 and

T, indoor unit will

select heating stage between indoor unit op-

eration and heater operation.

h

When the emergency heater setting is set

(installer code 18), emergency heater con-

trol operation is performed with priority.

Outdoor unit cycle priority
(Code 56)

It is the function to clear the limit and set the

operation mode when it is cleared, to be able

to select the operation mode opposite to the

operation mode of the outdoor unit currently

in operation while the connected product is in

Slave mode.

h

When you set installer code 08:00 (opera-

tion slave), according to the operation sta-

tus of the outdoor unit, cooling/heating

mode selection is restricted.

(T1 +

T < Outdoor temperature) :

only heat pump used

(T1 < Outdoor temperature < T1 +

T) :

both heater and heat pump used

(Outdoor temperature < T1) :
only heater used

1,MFL62862020,영영 2018. 1. 3. 영영 1:02 Page 32