INSTALLER SETTING

ENGLISH

INSTALLER SETTING

31

ENGLISH

Check indoor unit address number
(Code 26)

It is the function to verify the indoor unit ad-
dress designated by the outdoor unit.

Cooling thermal on/off setting
(Code 27)

It can adjust the cooling thermal on / off tem-
perature according to the field environment in
preparation for over cooling or cooling claim.

Setting temperature range (Code 31)

This function is used to select the tempera-
ture range options.

Value 00 (Default)

- Cooling : 64~86°F(18~30°C)

- Heating : 60~86°F(16~30°C)

Value 01

- Cooling : 64~99°F(18~37.5°C)

- Heating : 40~86°F(4~30°C)

NOTE

!

• In case of the setting expanded tem-

perature range (set), please note that
the setting of the wired remote con-
troller can be altered under below cir-
cumstances.

- In case of cooling at

87~99°F(30.5~37.5°C), it is changed
to cooling at 86°F(30°C).

- In case of heating at

40~59°F(4~15.5°C), it is changed to
heating at 60°F(16°C).

- If set on dual set points, it is changed

to the current operation mode(cooling
or heating) of the indoor unit.

Static pressure step
(Code 32)

This is the function that static pressure of the

product is divided in 11 steps for setting.

00 : Use static pressure(code 06) set value

01~ 11 : Use static pressure step (code 32)

set value

h

Refer to the product manual for information

on each step value.

h

This function is applied to only duct type.

h

Setting this in other cases will cause mal-

function.

CAUTION

This function setting must be carried out
by a certified-technician.

!

Value 1

18:00 : Disable emergency heater (Default)
18:01 : Enable emergency heater

When it connect general function indoor unit

When it connect extended function indoor
unit

Value 3

0 : Fan off
1 : Fan on (Fan is off when heater is off)

Value 2

Enable tempera-

ture

Disable tempera-

ture

Fahren-

heit (°F)

Celsius

(°C)

Fahren-

heit (°F)

Celsius

(°C)

0

Not used(Default)

1

0°F

-18°C

5°F

-15°C

2

5°F

-15°C

10°F

-12°C

3

10°F

-12°C

15°F

-9°C

Value 2

Enable tempera-

ture

Disable tempera-

ture

Fahren-

heit(°F)

Cel-

sius(°C)

Fahren-

heit(°F)

Cel-

sius(°C)

0

Not used(Default)

1

-10°F

-23°C

-5°F

-20°C

2

-5°F

-21°C

0°F

-17°C

3

0°F

-18°C

5°F

-14°C

4

5°F

-15°C

10°F

-11°C

5

10°F

-12°C

15°F

-8°C

6

15°F

-9°C

20°F

-5°C

7

20°F

-7°C

25°F

-2°C

8

25°F

-4°C

30°F

1°C

9

30°F

-1°C

35°F

4°C

10

35°F

2°C

40°F

7°C

11

40°F

4°C

45°F

10°C

12

45°F

7°C

50°F

13°C

13

50°F

10°C

55°F

16°C

14

55°F

13°C

60°F

19°C

15

60°F

16°C

65°F

22°C

Value

Thermal on

Thermal off

0

Default

(Different from each product)

1

12°F(6°C)

8°F(4°C)

2

8°F(4°C)

4°F(2°C)

3

2°F(1°C)

-2°F(-1°C)

Set point range lock (Code 34)

It is the function that can limit the range of the

desired temperature that can be set in the

wired remote controller.

When the temperature range is locked, the

desired temperature can be set only in the

range of the set value. But, the desired tem-

perature value by central control unit or addi-

tional accessories reflects the desired

temperature received beyond the range.

Operation mode

Set point upper limit

Set point lower limit

Lock enable / disable

Function code

h

Press button to select each function like
below.

Lock enable

/ disable

Operation

mode

Set point

lower limit

Set point

upper limit

Indoor unit

control

method

Code

31

Cooling

Heating

Single set

point

00

64~86 °F

(18~30 °C)

60~86 °F

(16~30 °C)

01

64~99 °F

(18~37.5 °C)

40~86 °F

(4~30 °C)

Dual set

points

-

50~99 °F

(10~37.5 °C)

40~90 °F

(4~32 °C)

1,MFL62862020,영영 2018. 1. 3. 영영 1:01 Page 30