INSTALLER SETTING

ENGLISH

INSTALLER SETTING

27

ENGLISH

Test run mode (Code 1)

After installing the product, you must run a Test run mode.

For details related to this operation, refer to the product manual.

00 : Normal operation (Default)

01 : Initiate cooling test mode

02 : Initiate heating test mode

During the test run, pressing the below button will exit the test run.

- On/Off, temp, fan speed, oper mode button.

Address setting (Code 2)

Sets the central control address of the indoor unit during the central controller connection.

XX : central control address number (00~FF)

E.S.P. function (Code 3)

Sets the wind amount value corresponding to each wind amount for easy installation.

[Select fan speed]

E.S.P value : 000~255

01 : Slow

02 : Low

03 : Middle

04 : High

05 : Power

h

Press button to select fan speed or

E.S.P value.

Function code

E.S.P value

Fan speed

NOTE

!

• Please be careful when adjusting ESP values.

• It does not work to setup ESP value for slow/power step for some products.

• ESP value range is dependent on product.

Temperature sensor setting (Code 4)

Determines if you will use the indoor unit mounted sensor or the remote controller sensor.

Temperature sensor selection

Function

01

Thermostat

Operate according to thermostat temperature sensor

02

Indoor unit

Operate according to indoor unit temperature sensor

03

2TH

Cooling

Operate according to higher temperature by comparing in-

door unit's and thermostat’s temperature. (There are

products that operate at a lower temperature.)

Heating

Operate according to lower temperature by comparing in-

door unit's and thermostat's temperature.

Ceiling height level

Description

01

Low

Decrease the indoor airflow rate 1 step from standard level

02

Standard

Set the indoor airflow rate as standard level

03

High

Increase indoor airflow rate 1 step from standard level

04

Very High

Increase indoor airflow rate 2 steps from standard level

Ceiling height (Code 5)

Controls the fan speed stage according to the ceiling height in the ceiling type product.

h

The function of 2TH has different operation characteristics according to the product.

h

Ceiling height setting is only available for some products.

h

Ceiling height of ‘Very high’ function may not exist depending on the indoor unit.

h

Refer to the product manual for more details.