INSTALLER SETTING

ENGLISH

INSTALLER SETTING

29

ENGLISH

Static pressure (Code 6)

Static pressure setting can be set only in the duct products. (It cannot be set in other products.)

Override master/slave setting (Code 8)

The operation master / slave selection function is to avoid other mode operations, and it is the

function to prevent the selection of opposite mode of the indoor unit master by the indoor units

set as slaves.

Dry contact mode setting (Code 9)

Dry contact function is the function that can be used only when the dry contact devices is sepa-

rately purchased and installed.

Emergency heater setting (Code 18)

This function is only available on some products.

This function will set the emergency heater setting.

Emergency heater is used to heat the space in emergency cases such as heat pump error.

Emergency heat is in place of and does not supplement heat pump.

h

Emergency heater setting function sets following conditions:

1) Emergency heater operation while in error or outdoor unit operating in the cooling cycle.

2) Emergency heater operation in low outdoor ambient temperature.

3) Fan speed setting during emergency heater operation.

Heating thermal on/off setting (Code 15)

You can adjust the heating on / off temperature according to the field environment in preparation
for over heating or heating claim.

Pressure selection

Function

Zone state

ESP standard value

01

V-H

Variable

High

02

F-H

Fixed

High

03

V-L

Variable

Low

04

F-L

Fixed

Low

M/S

Description

01

Master

Using group control, this master sets the mode of slave IDU’s.

02

Slave

For the indoor unit set as slave, it can only select the some operation

mode of the master indoor unit cycle.

Ex) Master is in cooling cycle, slave can select cooling, dehumidifica-

tion, auto, and wind only.

Master is in heating cycle, slave can select auto, heating, and wind

only.

NOTE

!

• Override M/S setting function is only available in some products.

NOTE

!

• For dry contact mode related detail functions, refer to the individual dry contact manual.

• What is dry contact?

- It means the contact point signal input when the hotel card key, human body detection

sensor, etc. are interfacing with the air conditioner.

- Added system functionality by using external inputs (dry contacts and wet contacts).

Function code

Value 2 : Low outdoor ambient heating operation

Value 3 : Fan speed setting during emergency heater operation

Value 1 : Heater operation while in error or outdoor unit operating

in the cooling cycle.

h

Press button to value 1, value 2 or value 3.

Value

Thermal on

Thermal off

0

Default(Different from each product)

1

8°F(4°C)

12°F(6°C)

2

4°F(2°C)

8°F(4°C)

3

-2°F(-1°C)

2°F(1°C)

4

-1°F(-0.5°C)

1°F(0.5°C)