LG Simple Remote Controller Thermostat Use and Care Guide User Manual

Page 12

background image

22

INSTALLER SETTING

ENGLISH

INSTALLER SETTING

23

ENGLISH

Code

No.

Function Name

Value

Description

26

Check indoor

unit

address number

XX(assigned address)

Display ODU assigned IDU address.

27

Cooling thermal

on/off setting

0: default, +1 °F/-1 °F(+0.5 °C/-0.5 °C)
1: +12 °F/+8 °F (+6 °C/+4 °C)
2: +8 °F/+4 °F (+4 °C/+2 °C)
3: +2 °F/-2 °F (+1 °C/-1 °C)

It can adjust the cooling thermal on / off
temperature according to the field environ-
ment in preparation for over cooling or
cooling claim.
*This function available from Gen 4 indoor

unit series.

29

Setting for refrig-

erant leak detec-

tor

00 : Not installed (Default)
01 : Installed

Enable this function after installing external
refrigerant leakage detection device.

30

SW version

Display remote SW version

Remote SW version

31

Setting tempera-

ture range

00 : 60~86°F(16~30°C) (Default)
01 : 40~99°F(4~37.5°C)

If the extended temperature range is set
refer to the following.
- Cooling 87~99°F (30.5~37.5°C) ->

86°F(30°C).

- Heating 40~59°F (4~15.5°C) ->

60°F(16°C).

- If set on dual set points, it is changed to

the current operation mode(cooling or
heating) of the indoor unit.

32

Static pressure

step

00 : Use static pressure (code 06) set

value (Default)

01~11 : Static pressure step (code 32)

set value

If code3 value(s) are changed from their de-
fault settings (000) then code32 values will
not be used.
Extended simplified air volume setting for
ducted product.

33

Guard timer

00 : 0 minute
01 : 15 minutes (Default)
02 : 30 minutes
03 : 45 minutes
04 : 60 minutes

Minimum time that must elapse before
system can change to opposite mode.
(example: change from heat to cool mode)

34

Set point range

lock

00 : Disable (Default)
01 : Enable

limits the heating and cooling setpoint
range that the user can select.
For more detail information see the follow-
ing instruction

35

Cooling thermal

off fan operation

00 : Fan low (Default)
01 : Fan off
02 : Previous fan setting

Set the fan speed operation during cooling
thermal off

36

Primary heater

control

00 : HP first stage heat (Default)
01 : HP last stage heat

Installer to select heat pump to operate as
first or last stage of heat with use of exter-
nal heat kit.

Code

No.

Function Name

Value

Description

12

Celsius /

Fahrenheit

switching

00 : Celsius
01 : Fahrenheit (Default)

Celsius or Fahrenheit.

15

Heating thermal

on/off setting

0: Default. Each indoor unit has differ-

ent value with product type.

1: +8 °F/+12 °F (+4 °C/+6 °C)
2: +4 °F/+8 °F (+2 °C/+4 °C)
3: -2 °F/ +2 °F (-1 °C/+1 °C)
4: -1 °F/ +1 °F (-0.5 °C /+0.5 °C)
*Option 4 is available under fahrenheit

unit use condition of code12.

It can adjust the heating thermal on / off
temperature according to the field environ-
ment in preparation for over heating or
heating claim.

17

Celsius tempera-

ture unit

00 : Celsius 1°C control (Default)
01 : Celsius 0.5°C control

Temperature resolution

18

Emergency

heater setting

[Value 1]
00 : Disable emergency heater

(Default)

01 : Enable emergency heater

[Value 2]
0 : Disable emergency heater in low

ambient temperature

1~15 : Enable emergency heater at low

ambient temperature

01 : -10F, 02 : -5F, 03 : 0F, 04 : 5F,
05 : 10F
06 : 15F, 07 : 20F, 08 : 25F, 09 : 30F,
10 : 35F
11 : 40F, 12 : 45F, 13 : 50F, 14 : 55F,
15 : 60F

[Value 3]
0 : Fan off
1 : Fan on (Fan is off when heater is off)

Setting value 1 enables auxiliary heater to
be used when ODU has an error code.
Setting value 2 enables ODU to be locked
out based on selected outside temperature
and enables auxiliary heater to be used.
Setting value 3 determines fan operation
during thermal on with auxiliary heater.

19

Function setting

in

group control

00 : Disable extended functions

(Default)

01 : Enable extended functions

Standard function : On/Off, Mode, Air
flow (Low/Mid/High), Set point, Schedule
Extended function: Air angle control(all),
Swirl, Air up/down, Air right/left, Energy
saving cooling, Fan Auto

20

Plasma purifica-

tion

00 : Disable
01 : Enable (Default)

It is a function to set whether Plasma pu-
rification is enable or not.

21

Auxiliary heat

control

00 : Manual heat control disabled
01 : Manual heat control enabled

(Default)

This setting allows user to enable/disable
the auxiliary heat in sub function menu.

25

External auxiliary

heat kit

00 : Not installed
01 : Installed (Default)

This function must be enabled to use exter-
nal auxiliary heat kit.

1,MFL62862020,영영 2018. 1. 3. 영영 1:01 Page 22