beautypg.com

Electrical requirements – u.s.a. only – Whirlpool 27 Inch Ventless Electric Dryer Installation Instructions User Manual

Page 6

background image

6

Laundry tub drain system

Minimum capacity: 20 gal. (76 L). Top of laundry tub must

be at least 30" (762 mm) above floor; install no higher than

54" (1.37 m) from bottom of dryer.

IMPORTANT:

Only 4.5" (114 mm) of drain hose should lay

on side of laundry tub. Do not lay the hose at the bottom of tub.

ELECTRICAL REQUIREMENTS –

U.S.A. ONLY

It is your responsibility:

To contact a qualified electrical installer.

To be sure that the electrical connection is adequate and

in conformance with the National Electrical Code, ANSI/

NFPA 70 – latest edition and all local codes and ordinances.

The National Electrical Code requires a 4-wire power supply

connection for homes built after 1996, dryer circuits involved

in remodeling after 1996, and all mobile home installations.

A copy of the above code standards can be obtained from:

National Fire Protection Association, One Batterymarch Park,

Quincy, MA 02269.

To supply the required 3- or 4-wire, single-phase, 120/240 V,

60 Hz, AC-only electrical supply (or 3- or 4-wire, 120/208 V

electrical supply, if specified on the serial/rating plate) on a

separate 30 A circuit, fused on both sides of the line. Connect

to an individual branch circuit. Do not have a fuse in the neutral

or grounding circuit.

Do not use an extension cord.

If codes permit and a separate ground wire is used, it is

recommended that a qualified electrician determine that

the ground path is adequate.

Remove the U-bend at the end of the drain hose by cutting

the hose at the end of the U-bend for the floor drain system

as shown in the picture above.

NOTE:

Cut hose so that no more than 4.5" (114 mm) of the hose

is in the floor drain to avoid siphoning.

Floor drain system

4.5"

(114 mm)

4.5"

(114 mm)

max. 54"

(1372 mm)

min. 30"

(762 mm)

If connecting by direct wire:

Power supply cable must match power supply (4-wire or 3-wire)

and be:

Flexible armored cable or nonmetallic sheathed copper cable

(with ground wire), covered with flexible metallic conduit.

All current-carrying wires must be insulated.

10-gauge solid copper wire (do not use aluminum) at least

5 ft. (1.52 m) long.

Then choose a 4-wire power supply cord with

ring or spade terminals and UL Listed strain

relief. The 4-wire power supply cord, at least

4 ft. (1.22 m) long, must have four 10-gauge

copper wires and match a 4-wire receptacle of

NEMA Type 14-30R. The ground wire (ground

conductor) may be either green or bare. The

neutral conductor must be identified by a white

cover.

Then choose a 3-wire power supply cord with

ring or spade terminals and UL Listed strain

relief. The 3-wire power supply cord, at least

4 ft. (1.22 m) long, must have three 10-gauge

copper wires and match a 3-wire receptacle

of NEMA Type 10-30R.

4-wire receptacle

(14-30R)

3-wire receptacle

(10-30R)

If your outlet looks like this:

Electrical Connection

To properly install your dryer, you must determine the type of

electrical connection you will be using and follow the instructions

provided for it here.

This dryer is manufactured ready to install with a 3-wire

electrical supply connection. The neutral ground conductor

is permanently connected to the neutral conductor (white wire)

within the dryer. If the dryer is installed with a 4-wire electrical

supply connection, the neutral ground conductor must be

removed from the external ground connector (green screw),

and secured under the neutral terminal (center or white wire)

of the terminal block. When the neutral ground conductor is

secured under the neutral terminal (center or white wire) of the

terminal block, the dryer cabinet is isolated from the neutral

conductor. The green ground wire of the 4-wire power cord

must be secured to the dryer cabinet with the green

ground screw.

If local codes do not permit the connection of a neutral

ground wire to the neutral wire, see the “Optional External

Ground for 3-Wire Connection” section.

A 4-wire power supply connection must be used when the

appliance is installed in a location where grounding through

the neutral conductor is prohibited. Grounding through the

neutral is prohibited for (1) new branch-circuit installations after

1996, (2) mobile homes, (3) recreational vehicles, and (4) areas

where local codes prohibit grounding through the neutral

conductors.

If using a power supply cord:

Use a UL Listed power supply cord kit marked for use with

clothes dryers. The kit should contain:

A UL Listed 30 A power supply cord, rated 120/240 V

minimum. The cord should be type SRD or SRDT and

be at least 4 ft. (1.22 m) long. The wires that connect to

the dryer must end in ring terminals or spade terminals

with upturned ends.

A UL Listed strain relief.